8 AWG wire: amps, diameter & uses

8 AWG copper is 0.1285" (3.26 mm) across and 8.37 mm², between 6 and 10 mm² metric. It is rated 40 / 50 / 55 A at 60 / 75 / 90 °C and takes a 50 A breaker. Used for 40 A ranges and cooktops, 40–50 A circuits in conduit.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · caliper

8 AWG · bare solid copper

THIS IS:

8 AWG COPPER · 50 A BREAKER · 3.26 MM COPPER

Gauge
8 AWG
bare solid copper
Breaker
50 A
copper, max
Measured
3.26 mm
0.1285"

The gap is 3.26 mm (0.1285"), which reads as 8 AWG bare solid copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

8 AWG

Solid diameter
0.128"3.26 mm · ASTM B258 formula
Stranded (7 strands)
0.146"3.71 mm · Table 8
THHN outside
0.216"5.49 mm · 0.0366 in² · Table 5
Area
16,510 cmil8.37 mm² · nearest IEC 10 mm²
DC resistance, 75 °C
0.778 Ω/1000 ftaluminum 1.28 Ω/1000 ft · Table 8
Copper weight
50.0 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
40 / 50 / 55 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
35 / 40 / 45 A
Largest breaker (Cu, 75 °C)
50 Aampacity ≥ breaker

Other gauges

Nearest SWG
SWG 100.128" · 3.251 mm
IEC 60228
10 mm²between 6 and 10 mm²

8 AWG at a glance

Size

Solid diameter
0.1285" · 3.26 mm
Stranded (7)
0.146"
THHN outside
0.216"
Area
16,510 cmil · 8.37 mm²
Metric
6 – 10 mm²
SWG nearest
10 (3.251 mm)

Amps

Copper 60/75/90 °C
40 / 50 / 55 A
Aluminum 75 °C
40 A
Max breaker, THHN
50 A
As NM-B cable
40 A · black
Ground for it
10 AWG

Run & fit

120 V at 40 A
57 ft at 3 %
240 V at 40 A
115 ft at 3 %
THHN in ½" EMT
3
THHN in ¾" EMT
6
Copper weight
50.0 lb/1000 ft

8 AWG reference 22 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

8 AWG
the branch-circuit size.

8 AWG copper is 0.1285" (3.26 mm) across and 8.37 mm², between 6 and 10 mm² metric. It is rated 40 / 50 / 55 A at 60 / 75 / 90 °C and takes a 50 A breaker. Used for 40 A ranges and cooktops, 40–50 A circuits in conduit.

Between its neighbours

8 AWG has 59 % more copper than 10 AWG and 37 % less than 6 AWG. Its DC resistance is 0.778 Ω per 1000 ft at 75 °C (aluminum 1.28), and 1000 ft of it carries 50.0 lb of copper.

Circuits it is used for

8 AWG is the usual choice for 40 A ranges and cooktops, 40–50 A circuits in conduit. As NM-B it comes as 8/2 and 8/3 with a black jacket, held to the 60 °C column (40 A). The equipment ground for its largest breaker is 10 AWG.

On the 1:1 gauge

The caliper above opens at 3.26 mm. Lay a stripped length along the lines and step the gauge with ← and → until the wire just fills the gap.

Questions

Answered plainly.

01

How many amps can 8 AWG wire carry?

+

8 AWG copper is rated 40 A at 60 °C, 50 A at 75 °C and 55 A at 90 °C (NEC Table 310.16, 30 °C, three conductors or fewer). Aluminum of the same size: 40 A at 75 °C.

02

What size breaker for 8 AWG wire?

+

Up to 50 A with THHN on 75 °C terminals, 40 A as NM-B cable (60 °C); the next size up is allowed by 240.4(B) only where the ampacity is not itself a standard rating.

03

What is the diameter of 8 AWG wire?

+

0.1285 inch (3.26 mm) solid, 0.146 inch stranded (7 strands), about 0.216 inch with THHN insulation.

04

What is 8 AWG in mm²?

+

8.37 mm² (16,510 circular mils). The IEC sizes either side are 6 and 10 mm²; replace it with 10 mm², not the smaller one.

05

How far can 8 AWG wire run?

+

At 40 A and 3 % drop, 57 ft one way at 120 V and 115 ft at 240 V (Table 8 resistance, 0.778 Ω per 1000 ft at 75 °C). Lighter loads go proportionally further.

06

How many 8 AWG wires fit in ½" EMT?

+

3 THHN conductors in ½" EMT, 6 in ¾" and 9 in 1" (NEC Chapter 9, 40 % fill for three or more).

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →