12 AWG wire: amps, diameter & uses

12 AWG copper is 0.0808" (2.05 mm) across and 3.31 mm², between 2.5 and 4 mm² metric. It is rated 20 / 25 / 30 A at 60 / 75 / 90 °C and takes a 20 A breaker (the 240.4(D) cap). Used for 20 A kitchen, bathroom, laundry and garage receptacle circuits.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · caliper

12 AWG · bare solid copper

THIS IS:

12 AWG COPPER · 20 A BREAKER · 2.05 MM COPPER

Gauge
12 AWG
bare solid copper
Breaker
20 A
copper, max
Measured
2.05 mm
0.0808"

The gap is 2.05 mm (0.0808"), which reads as 12 AWG bare solid copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

12 AWG

Solid diameter
0.0808"2.053 mm · ASTM B258 formula
Stranded (7 strands)
0.0920"2.337 mm · Table 8
THHN outside
0.130"3.30 mm · 0.0133 in² · Table 5
Area
6,530 cmil3.31 mm² · nearest IEC 4 mm²
DC resistance, 75 °C
1.98 Ω/1000 ftaluminum 3.25 Ω/1000 ft · Table 8
Copper weight
19.8 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
20 / 25 / 30 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
15 / 20 / 25 A
Largest breaker (Cu, 75 °C)
20 A240.4(D) small-conductor cap

Other gauges

Nearest SWG
SWG 140.08" · 2.032 mm
IEC 60228
4 mm²between 2.5 and 4 mm²

12 AWG at a glance

Size

Solid diameter
0.0808" · 2.05 mm
Stranded (7)
0.092"
THHN outside
0.13"
Area
6,530 cmil · 3.31 mm²
Metric
2.5 – 4 mm²
SWG nearest
14 (2.032 mm)

Amps

Copper 60/75/90 °C
20 / 25 / 30 A
Aluminum 75 °C
20 A
Max breaker, THHN
20 A
As NM-B cable
20 A · yellow
Ground for it
12 AWG

Run & fit

120 V at 16 A
56 ft at 3 %
240 V at 16 A
113 ft at 3 %
THHN in ½" EMT
9
THHN in ¾" EMT
16
Copper weight
19.8 lb/1000 ft

12 AWG reference 21 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

12 AWG
the branch-circuit size.

12 AWG copper is 0.0808" (2.05 mm) across and 3.31 mm², between 2.5 and 4 mm² metric. It is rated 20 / 25 / 30 A at 60 / 75 / 90 °C and takes a 20 A breaker (the 240.4(D) cap). Used for 20 A kitchen, bathroom, laundry and garage receptacle circuits.

Between its neighbours

12 AWG has 59 % more copper than 14 AWG and 37 % less than 10 AWG. Its DC resistance is 1.98 Ω per 1000 ft at 75 °C (aluminum 3.25), and 1000 ft of it carries 19.8 lb of copper.

Circuits it is used for

12 AWG is the usual choice for 20 A kitchen, bathroom, laundry and garage receptacle circuits. As NM-B it comes as 12/2 and 12/3 with a yellow jacket, held to the 60 °C column (20 A). The equipment ground for its largest breaker is 12 AWG.

On the 1:1 gauge

The caliper above opens at 2.05 mm. Lay a stripped length along the lines and step the gauge with ← and → until the wire just fills the gap.

Questions

Answered plainly.

01

How many amps can 12 AWG wire carry?

+

12 AWG copper is rated 20 A at 60 °C, 25 A at 75 °C and 30 A at 90 °C (NEC Table 310.16, 30 °C, three conductors or fewer). 240.4(D) still limits it to a 20 A breaker. Aluminum of the same size: 20 A at 75 °C.

02

What size breaker for 12 AWG wire?

+

Up to 20 A with THHN on 75 °C terminals, 20 A as NM-B cable (60 °C).

03

What is the diameter of 12 AWG wire?

+

0.0808 inch (2.05 mm) solid, 0.092 inch stranded (7 strands), about 0.13 inch with THHN insulation.

04

What is 12 AWG in mm²?

+

3.31 mm² (6,530 circular mils). The IEC sizes either side are 2.5 and 4 mm²; replace it with 4 mm², not the smaller one.

05

How far can 12 AWG wire run?

+

At 16 A and 3 % drop, 56 ft one way at 120 V and 113 ft at 240 V (Table 8 resistance, 1.98 Ω per 1000 ft at 75 °C). Lighter loads go proportionally further.

06

How many 12 AWG wires fit in ½" EMT?

+

9 THHN conductors in ½" EMT, 16 in ¾" and 26 in 1" (NEC Chapter 9, 40 % fill for three or more).

07

How far can 12 AWG speaker wire run?

+

About 125 ft to an 8 Ω speaker and 62 ft to a 4 Ω one before the cable passes 5 % of the impedance (about 0.42 dB).

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →