Three columns, three answers
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 6 AWG NM-B and 8 AWG THHN can both serve 50 A.
A 50 A circuit takes 6 AWG NM-B in the wall or 8 AWG copper THHN in conduit (75 °C), with a 10 AWG ground; aluminum needs 6 AWG. At an 40 A load the copper reaches 115 ft at 240 V (3 % drop). Used for ranges, hot tubs, welders and 40 A EV chargers (NEMA 14-50).
02 · Ampacity · NEC 2023 Table 310.16
USE:
8 AWG COPPER · 50 A ALLOWABLE · 50 A MAX BREAKER
8 AWG copper carries 55 A after derating from the 90 °C column and 50 A at its 75 °C terminals, so it is good for 50 A on a breaker up to 50 A.
Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.
| Actions | |||||
|---|---|---|---|---|---|
| 6 AWG | 6 AWG | 10 AWG | 183 ft | ||
| 8 AWG | 8 AWG | 10 AWG | 115 ft | ||
| 6 AWG | 6 AWG | 8 AWG | 111 ft |
Feet one way (the current goes out and back). Ampacity is a separate check: a long run may need a heavier wire for drop, never a lighter one for heat.
05 / Field guide
A 50 A circuit takes 6 AWG NM-B in the wall or 8 AWG copper THHN in conduit (75 °C), with a 10 AWG ground; aluminum needs 6 AWG. At an 40 A load the copper reaches 115 ft at 240 V (3 % drop). Used for ranges, hot tubs, welders and 40 A EV chargers (NEMA 14-50).
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 6 AWG NM-B and 8 AWG THHN can both serve 50 A.
240.4(B) lets a conductor whose ampacity is not a standard size take the next breaker up (not on multi-outlet receptacle circuits). The headline here uses ampacity at least 50 A.
The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.
Questions
6 AWG copper NM-B in the wall, 8 AWG copper THHN in conduit or 6 AWG aluminum, all with ampacity at least 50 A (NEC 2023 Table 310.16).
Not at the ampacity rule: NM-B is limited to the 60 °C column (334.80), where 8 AWG carries 40 A; use 6 AWG.
10 AWG copper or 8 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).
At 40 A (80 %) on 8 AWG copper, 115 ft one way at 240 V or 57 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.
40 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).