What size wire for 30 amps?

A 30 A circuit takes 10 AWG NM-B in the wall or 10 AWG copper THHN in conduit (75 °C), with a 10 AWG ground; aluminum needs 8 AWG. At an 24 A load the copper reaches 120 ft at 240 V (3 % drop). Used for clothes dryers, water heaters and 30 A RV outlets.

Drawing at true size…

02 · Ampacity · NEC 2023 Table 310.16

10 AWG copper · 90 °C insulation, 75 °C terminals, 30 °C, 3 conductors

USE:

10 AWG COPPER · 35 A ALLOWABLE · 30 A MAX BREAKER

Allowable
35 A
10 AWG Cu
Max breaker
30 A
240.4(D) cap
For your load
10 AWG
30 A

10 AWG copper carries 40 A after derating from the 90 °C column and 35 A at its 75 °C terminals, so it is good for 35 A on a breaker up to 30 A.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector110.14(C)
  • Load 30 A ≤ 35 A310.14

Derating math

Table 310.16 at 90 °C
40 Aderating starts at the insulation rating
Ambient factor
× 1.0030 °C, Table 310.15(B)(1)
Bundling factor
× 1.003 current-carrying conductors, 310.15(C)(1)
Derated
40 A
Terminal limit (75 °C)
35 A110.14(C)
Allowable
35 Athe terminals decide

10 AWG

Copper 60 / 75 / 90 °C
30 / 35 / 40 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
25 / 30 / 35 A
Largest breaker (Cu, 75 °C)
30 A240.4(D) small-conductor cap
Solid diameter
0.102"2.59 mm · ASTM B258 formula
Stranded (7 strands)
0.116"2.95 mm · Table 8
THHN outside
0.164"4.17 mm · 0.0211 in² · Table 5
Area
10,380 cmil5.26 mm² · nearest IEC 6 mm²
DC resistance, 75 °C
1.24 Ω/1000 ftaluminum 2.04 Ω/1000 ft · Table 8
Copper weight
31.4 lb/1000 ft

30 A circuit at a glance

Wire

Copper NM-B (60 °C)
10 AWG
Copper THHN (75 °C)
10 AWG
Aluminum (75 °C)
8 AWG

Ground & breaker

Copper ground
10 AWG
Aluminum ground
8 AWG
Continuous load max
24 A
Breaker
30 A

Distance (3 %)

Cu at 120 V, 24 A
60 ft
Cu at 240 V, 24 A
120 ft
Al at 240 V, 24 A
117 ft

30 A circuit tables 8 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

30 amps:
which wire, which method.

A 30 A circuit takes 10 AWG NM-B in the wall or 10 AWG copper THHN in conduit (75 °C), with a 10 AWG ground; aluminum needs 8 AWG. At an 24 A load the copper reaches 120 ft at 240 V (3 % drop). Used for clothes dryers, water heaters and 30 A RV outlets.

Three columns, three answers

NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 10 AWG NM-B and 10 AWG THHN can both serve 30 A.

Breaker rules

240.4(D) fixes the small sizes: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A, whatever the ampacity table allows.

Distance

The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.

Questions

Answered plainly.

01

What size wire for a 30 amp breaker?

+

10 AWG copper NM-B in the wall, 10 AWG copper THHN in conduit or 8 AWG aluminum, all with ampacity at least 30 A (NEC 2023 Table 310.16).

02

Can I use 10 AWG wire on a 30 amp breaker in NM-B cable?

+

Yes: 10 AWG NM-B is rated 30 A at 60 °C.

03

What size ground wire for 30 amps?

+

10 AWG copper or 8 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).

04

How far can I run a 30 amp circuit?

+

At 24 A (80 %) on 10 AWG copper, 120 ft one way at 240 V or 60 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.

05

What is the largest continuous load on a 30 amp circuit?

+

24 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).

Browse all 20 gauges, 12 conduit sizes and 10 circuits