wire&amp home

Printable 1:1 wire stripper gauge & shop charts

Printable wire gauge: a true-size stripper notch card from 4/0 to 24 AWG, the NEC Table 310.16 chart and an EMT fill chart on one page. Print at 100 %, check the 50 mm bar, then test a wire in the notches. No printer? The on-screen comb above draws the same notches at 1:1.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · stripper comb

12 AWG · concentric stranded copper

THIS IS:

12 AWG COPPER · 20 A BREAKER · 2.05 MM COPPER

Gauge
12 AWG
concentric stranded copper
Breaker
20 A
copper, max
Measured
2.34 mm
0.0920"

The gap is 2.34 mm (0.0920"), which reads as 12 AWG concentric stranded copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

12 AWG

Solid diameter
0.0808"2.053 mm · ASTM B258 formula
Stranded (7 strands)
0.0920"2.337 mm · Table 8
THHN outside
0.130"3.30 mm · 0.0133 in² · Table 5
Area
6,530 cmil3.31 mm² · nearest IEC 4 mm²
DC resistance, 75 °C
1.98 Ω/1000 ftaluminum 3.25 Ω/1000 ft · Table 8
Copper weight
19.8 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
20 / 25 / 30 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
15 / 20 / 25 A
Largest breaker (Cu, 75 °C)
20 A240.4(D) small-conductor cap

Other gauges

Nearest SWG
SWG 130.092" · 2.337 mm
IEC 60228
4 mm²between 2.5 and 4 mm²

Print at 100 % (actual size), then measure the control bar: it must be exactly 50 mm. Slide a stripped wire into the first notch it fits; widths are Table 8 stranded diameters, so solid wire drops one notch further.

4/03/02/01/0123468101214161820222413.411.910.69.48.47.46.65.94.73.72.92.31.91.51.20.80.60.5control bar: must measure 50 mm · notch widths in mm

Printable shop charts 46 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

Paper that
stays true.

A printed gauge is only as good as the print scale. Print at 100 % (not “fit to page”) and measure the 50 mm control bar before trusting a notch; most printers hold scale within half a percent when set correctly.

The stripper card

Notches from 4/0 to 24 AWG at true width for stranded copper; slide a stripped wire into the first notch it fits. The NEC Table 310.16 chart and the ½"–2" EMT fill chart print on the same sheet for the shop wall.

On screen instead

The on-screen comb draws the same notches at 1:1 after you calibrate with a coin or a card, and the fullscreen mat adds conduit outside diameters.

Why the screen can be trusted

A browser does not know how big its pixels are, so the gauge starts from a table of 114 phones, tablets, laptops and monitors matched to your screen’s size and pixel ratio, an estimate good to about five percent. Laying a coin or a bank card on the glass and matching its outline replaces the estimate with a measurement good to a fraction of a percent, saved for this screen only.

Browser zoom is corrected automatically from the pixel ratio; pinch zoom is flagged, because nothing drawn is true size until it is undone.

pixels per mm = CSS px across the card ÷ 85.60 mm ID-1 card: 85.60 × 53.98 mm (ISO/IEC 7810)

Getting a true-size print

Print from a desktop browser or the PDF, at 100 % or “actual size”, with headers and footers off. Phones and some print dialogs shrink the page to fit the margins; that is the most common cause of a card that measures 48 mm instead of 50 mm. If the control bar is off, the error is the same percentage everywhere on the sheet, so fix the scale and reprint rather than correcting by eye.

Card stock or a laminated sheet lasts longer in a tool bag; cut the notches with a sharp blade along the printed lines.

Using the notch card safely

Only test de-energised wire. Strip a short length and slide the bare copper into the notches from the largest down; the first notch it will not enter is one size too small. Stranded wire that has been crushed or twisted reads one size larger, so test an end you have just cut.

Questions

Answered plainly.

01

How do I print at true size?

+

Choose 100 % or “actual size” in the print dialog, turn off “fit to page”, then measure the 50 mm bar with a ruler.

02

Can I laminate the chart?

+

Yes; lamination adds a few tenths of a millimetre of plastic, so read wire fits by the notch edges, not the laminate.

03

Why stranded widths?

+

Most building wire 8 AWG and up is stranded; Table 8 stranded diameters are slightly larger than solid ones, so a solid wire will drop one notch further.

04

Is the printed ampacity chart the full table?

+

Copper, 14 AWG to 500 kcmil, at 60, 75 and 90 °C, with the largest breaker each may take; aluminum and derating are on the ampacity page.

05

Letter or A4?

+

Either: nothing on the sheet depends on the paper size, only on printing at 100 %.

06

My printed control bar is 48 mm. What went wrong?

+

The page was scaled down, usually by “fit to page” or a phone’s print dialog. Print at 100 % from a desktop browser and check the bar again.

07

Can I use the card on insulated wire?

+

No, it is cut for bare copper. Use the insulated profile of the on-screen gauge to compare a jacket’s outside diameter.

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →