What size wire for 100 amps?

A 100 A feeder takes 3 AWG copper or 1 AWG aluminum at 75 °C with a 8 AWG copper ground. A house service (or the feeder carrying the whole house) may use the 83 % rule: 4 AWG copper or 2 AWG aluminum. A 100 A subpanel feeder does not get it.

Drawing at true size…

02 · Ampacity · NEC 2023 Table 310.16

3 AWG copper · 90 °C insulation, 75 °C terminals, 30 °C, 3 conductors

USE:

3 AWG COPPER · 100 A ALLOWABLE · 100 A MAX BREAKER

Allowable
100 A
3 AWG Cu
Max breaker
100 A
ampacity ≥ breaker
For your load
3 AWG
100 A

3 AWG copper carries 115 A after derating from the 90 °C column and 100 A at its 75 °C terminals, so it is good for 100 A on a breaker up to 100 A.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector110.14(C)
  • Load 100 A ≤ 100 A310.14

Derating math

Table 310.16 at 90 °C
115 Aderating starts at the insulation rating
Ambient factor
× 1.0030 °C, Table 310.15(B)(1)
Bundling factor
× 1.003 current-carrying conductors, 310.15(C)(1)
Derated
115 A
Terminal limit (75 °C)
100 A110.14(C)
Allowable
100 Athe terminals decide

3 AWG

Copper 60 / 75 / 90 °C
85 / 100 / 115 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
65 / 75 / 85 A
Largest breaker (Cu, 75 °C)
100 Aampacity ≥ breaker
Solid diameter
0.229"5.83 mm · ASTM B258 formula
Stranded (7 strands)
0.260"6.60 mm · Table 8
THHN outside
0.352"8.94 mm · 0.0973 in² · Table 5
Area
52,620 cmil26.66 mm² · nearest IEC 25 mm²
DC resistance, 75 °C
0.245 Ω/1000 ftaluminum 0.403 Ω/1000 ft · Table 8
Copper weight
159.3 lb/1000 ft

100 A circuit at a glance

Wire

Copper NM-B (60 °C)
2 AWG (next size up)
Copper THHN (75 °C)
3 AWG
Aluminum (75 °C)
1 AWG

Ground & breaker

Copper ground
8 AWG
Aluminum ground
6 AWG
Continuous load max
80 A
Breaker
100 A

Distance (3 %)

Cu at 120 V, 80 A
91 ft
Cu at 240 V, 80 A
183 ft
Al at 240 V, 80 A
177 ft

100 A circuit tables 12 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

100 amps:
feeder or service?

A 100 A feeder takes 3 AWG copper or 1 AWG aluminum at 75 °C with an 8 AWG copper ground. A house service (or the feeder carrying the whole house) may use the 83 % rule: 4 AWG copper or 2 AWG aluminum. A 100 A subpanel feeder does not get it.

Three columns, three answers

NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. NM-B is made only up to 2 AWG copper, so a 100 A circuit runs as THHN, XHHW or SER.

Breaker rules

240.4(B) lets a conductor whose ampacity is not a standard size take the next breaker up (not on multi-outlet receptacle circuits). The headline here uses ampacity at least 100 A.

Distance

The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.

Questions

Answered plainly.

01

What size wire for a 100 amp breaker?

+

3 AWG copper THHN in conduit or 1 AWG aluminum, all with ampacity at least 100 A (NEC 2023 Table 310.16).

02

Can I use 3 AWG wire on a 100 amp breaker in NM-B cable?

+

Not at the ampacity rule: NM-B is limited to the 60 °C column (334.80), where 3 AWG carries 85 A; use conduit.

03

What size ground wire for 100 amps?

+

8 AWG copper or 6 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).

04

How far can I run a 100 amp circuit?

+

At 80 A (80 %) on 3 AWG copper, 183 ft one way at 240 V or 91 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.

05

What is the largest continuous load on a 100 amp circuit?

+

80 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).

06

Can 4 AWG copper be used for 100 amps?

+

For a dwelling’s 100 A service, or the feeder carrying the whole dwelling, yes (310.12, 83 %). For a 100 A subpanel feeder, no: use 3 AWG copper or 1 AWG aluminum.