Speaker cable steals power by adding resistance in series with the speaker. Keep the out-and-back resistance under 5 % of the speaker’s nominal impedance and the loss stays near 0.4 dB, below what anyone hears; lower-impedance speakers need heavier wire for the same distance.
The loss
For a resistive load the speaker gets Z ÷ (Z + R) of the voltage, so the loss in decibels is 20·log10 of that. 5 % of Z is 0.42 dB; 12 % is 1 dB. 16 AWG copper to an 8 Ω speaker reaches 49 ft for 5 % and 121 ft for 1 dB.
loss dB = 20 · log10( Z ÷ (Z + R) ) R = 2 × L × r (Ω/ft) 5 % rule: R ≤ 0.05 × Z
OFC and CCA
Oxygen-free copper and ordinary annealed copper both sit at about 100 % IACS conductivity, so their resistance is the same for speaker runs; OFC’s case is corrosion and flexibility, not sound. Copper-clad aluminum is different: ASTM B566 class 10A conducts 62.9 % of copper, so it has 1.59 times the resistance of copper of the same gauge.
Damping factor
An amplifier’s damping factor is speaker impedance over its output impedance. Cable resistance adds to the output side, so a 200 DF amp into 8 Ω through 0.4 Ω of cable delivers a damping factor near 18 at the speaker; above about 10–20 the difference is hard to hear.
In-wall runs and long distances
Speaker cable inside a wall or ceiling must be listed for it: look for a CL2 or CL3 marking (power-limited cable, NEC Article 722 in the 2023 edition). Ordinary zip cord is for exposed runs only. Through a fire-rated wall or a plenum, the cable needs the matching rating (CL2P or CMP).
Gauge matters most with low-impedance speakers. At 4 Ω the 5 % rule allows 24 ft of 16 AWG, 39 ft of 14 AWG and 62 ft of 12 AWG; at 8 Ω every figure doubles. Bi-wiring a speaker doubles the copper too, which halves the loop resistance.
70 V and 100 V systems
Commercial background-music systems run their speaker lines at 70 V or 100 V through step-down transformers at each speaker. The current is small, so 16 or 18 AWG covers long runs that would need heavy cable at 8 Ω; those runs are sized by power and distance from the system maker’s tables, not by this chart.