What size wire for 15 amps?

A 15 A circuit takes 14 AWG NM-B in the wall or 14 AWG copper THHN in conduit (75 °C), with a 14 AWG ground; aluminum needs 12 AWG. At an 12 A load the copper reaches 95 ft at 240 V (3 % drop). Used for general lighting and bedroom receptacles.

Drawing at true size…

02 · Ampacity · NEC 2023 Table 310.16

14 AWG copper · 90 °C insulation, 75 °C terminals, 30 °C, 3 conductors

USE:

14 AWG COPPER · 20 A ALLOWABLE · 15 A MAX BREAKER

Allowable
20 A
14 AWG Cu
Max breaker
15 A
240.4(D) cap
For your load
14 AWG
15 A

14 AWG copper carries 25 A after derating from the 90 °C column and 20 A at its 75 °C terminals, so it is good for 20 A on a breaker up to 15 A.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector110.14(C)
  • Load 15 A ≤ 20 A310.14

Derating math

Table 310.16 at 90 °C
25 Aderating starts at the insulation rating
Ambient factor
× 1.0030 °C, Table 310.15(B)(1)
Bundling factor
× 1.003 current-carrying conductors, 310.15(C)(1)
Derated
25 A
Terminal limit (75 °C)
20 A110.14(C)
Allowable
20 Athe terminals decide

14 AWG

Copper 60 / 75 / 90 °C
15 / 20 / 25 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
—
Largest breaker (Cu, 75 °C)
15 A240.4(D) small-conductor cap
Solid diameter
0.0641"1.628 mm · ASTM B258 formula
Stranded (7 strands)
0.0730"1.854 mm · Table 8
THHN outside
0.111"2.82 mm · 0.0097 in² · Table 5
Area
4,110 cmil2.08 mm² · nearest IEC 2.5 mm²
DC resistance, 75 °C
3.14 Ω/1000 ftaluminum 5.17 Ω/1000 ft · Table 8
Copper weight
12.4 lb/1000 ft

15 A circuit at a glance

Wire

Copper NM-B (60 °C)
14 AWG
Copper THHN (75 °C)
14 AWG
Aluminum (75 °C)
12 AWG

Ground & breaker

Copper ground
14 AWG
Aluminum ground
12 AWG
Continuous load max
12 A
Breaker
15 A

Distance (3 %)

Cu at 120 V, 12 A
47 ft
Cu at 240 V, 12 A
95 ft
Al at 240 V, 12 A
92 ft

15 A circuit tables 7 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

15 amps:
which wire, which method.

A 15 A circuit takes 14 AWG NM-B in the wall or 14 AWG copper THHN in conduit (75 °C), with a 14 AWG ground; aluminum needs 12 AWG. At an 12 A load the copper reaches 95 ft at 240 V (3 % drop). Used for general lighting and bedroom receptacles.

Three columns, three answers

NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 14 AWG NM-B and 14 AWG THHN can both serve 15 A.

Breaker rules

240.4(D) fixes the small sizes: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A, whatever the ampacity table allows.

Distance

The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.

Questions

Answered plainly.

01

What size wire for a 15 amp breaker?

+

14 AWG copper NM-B in the wall, 14 AWG copper THHN in conduit or 12 AWG aluminum, all with ampacity at least 15 A (NEC 2023 Table 310.16).

02

Can I use 14 AWG wire on a 15 amp breaker in NM-B cable?

+

Yes: 14 AWG NM-B is rated 15 A at 60 °C.

03

What size ground wire for 15 amps?

+

14 AWG copper or 12 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).

04

How far can I run a 15 amp circuit?

+

At 12 A (80 %) on 14 AWG copper, 95 ft one way at 240 V or 47 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.

05

What is the largest continuous load on a 15 amp circuit?

+

12 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →