2 AWG wire: amps, diameter & uses

2 AWG copper is 0.2576" solid (0.292" as 7-strand) and 33.6 mm². Table 310.16 rates it 95 / 115 / 130 A at 60 / 75 / 90 °C, so it protects up to a 110 A breaker on 75 °C terminals; aluminum of this size carries 90 A. Typical use: 100–125 A feeders, 2/3 NM-B and large inverter cables.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · caliper

2 AWG · concentric stranded copper

THIS IS:

2 AWG COPPER · 110 A BREAKER · 6.54 MM COPPER

Gauge
2 AWG
concentric stranded copper
Breaker
110 A
copper, max
Measured
7.42 mm
0.2920"

The gap is 7.42 mm (0.2920"), which reads as 2 AWG concentric stranded copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

2 AWG

Solid diameter
0.258"6.54 mm · ASTM B258 formula
Stranded (7 strands)
0.292"7.42 mm · Table 8
THHN outside
0.384"9.75 mm · 0.1158 in² · Table 5
Area
66,360 cmil33.63 mm² · nearest IEC 35 mm²
DC resistance, 75 °C
0.194 Ω/1000 ftaluminum 0.319 Ω/1000 ft · Table 8
Copper weight
200.9 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
95 / 115 / 130 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
75 / 90 / 100 A
Largest breaker (Cu, 75 °C)
110 Aampacity ≥ breaker

Other gauges

Nearest SWG
SWG 10.3" · 7.62 mm
IEC 60228
35 mm²between 25 and 35 mm²

2 AWG at a glance

Size

Solid diameter
0.2576" · 6.54 mm
Stranded (7)
0.292"
THHN outside
0.384"
Area
66,360 cmil · 33.63 mm²
Metric
25 – 35 mm²
SWG nearest
3 (6.401 mm)

Amps

Copper 60/75/90 °C
95 / 115 / 130 A
Aluminum 75 °C
90 A
Max breaker, THHN
110 A
As NM-B cable
not made
Ground for it
6 AWG

Run & fit

120 V at 88 A
105 ft at 3 %
240 V at 88 A
210 ft at 3 %
THHN in ½" EMT
1
THHN in ¾" EMT
1
Copper weight
200.9 lb/1000 ft

2 AWG reference 25 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

2 AWG
feeder copper.

2 AWG copper is 0.2576" solid (0.292" as 7-strand) and 33.6 mm². Table 310.16 rates it 95 / 115 / 130 A at 60 / 75 / 90 °C, so it protects up to a 110 A breaker on 75 °C terminals; aluminum of this size carries 90 A. Typical use: 100–125 A feeders, 2/3 NM-B and large inverter cables.

Between its neighbours

2 AWG has 26 % more copper than 3 AWG and 21 % less than 1 AWG. Its DC resistance is 0.194 Ω per 1000 ft at 75 °C (aluminum 0.319), and 1000 ft of it carries 200.9 lb of copper.

Feeders and services

2 AWG is the usual choice for 100–125 A feeders, 2/3 NM-B and large inverter cables. It is not made as NM-B cable; use THHN or XHHW in conduit, or SER/USE cable. The equipment ground for its largest breaker is 6 AWG.

On the 1:1 gauge

The caliper above opens at 6.54 mm. Lay a stripped length along the lines and step the gauge with ← and → until the wire just fills the gap.

Questions

Answered plainly.

01

How many amps can 2 AWG wire carry?

+

2 AWG copper is rated 95 A at 60 °C, 115 A at 75 °C and 130 A at 90 °C (NEC Table 310.16, 30 °C, three conductors or fewer). Aluminum of the same size: 90 A at 75 °C.

02

What size breaker for 2 AWG wire?

+

Up to 110 A with THHN on 75 °C terminals; the next size up is allowed by 240.4(B) only where the ampacity is not itself a standard rating.

03

What is the diameter of 2 AWG wire?

+

0.2576 inch (6.54 mm) solid, 0.292 inch stranded (7 strands), about 0.384 inch with THHN insulation.

04

What is 2 AWG in mm²?

+

33.63 mm² (66,360 circular mils). The IEC sizes either side are 25 and 35 mm²; replace it with 35 mm², not the smaller one.

05

How far can 2 AWG wire run?

+

At 88 A and 3 % drop, 105 ft one way at 120 V and 210 ft at 240 V (Table 8 resistance, 0.194 Ω per 1000 ft at 75 °C). Lighter loads go proportionally further.

06

How many 2 AWG wires fit in ½" EMT?

+

1 THHN conductors in ½" EMT, 1 in ¾" and 3 in 1" (NEC Chapter 9, 40 % fill for three or more).

07

Can 2 AWG be used for a house service?

+

Yes: by the 83 % rule (310.12) 2 AWG copper serves a dwelling’s 125 A service, or the feeder carrying its whole load. A subpanel feeder does not get the 83 % rule.

Browse all 20 gauges, 12 conduit sizes and 10 circuits