What size wire for 20 amps?

A 20 A circuit takes 12 AWG NM-B in the wall or 12 AWG copper THHN in conduit (75 °C), with a 12 AWG ground; aluminum needs 10 AWG. At an 16 A load the copper reaches 113 ft at 240 V (3 % drop). Used for kitchen, bathroom, laundry and garage receptacles.

Drawing at true size…

02 · Ampacity · NEC 2023 Table 310.16

12 AWG copper · 90 °C insulation, 75 °C terminals, 30 °C, 3 conductors

USE:

12 AWG COPPER · 25 A ALLOWABLE · 20 A MAX BREAKER

Allowable
25 A
12 AWG Cu
Max breaker
20 A
240.4(D) cap
For your load
12 AWG
20 A

12 AWG copper carries 30 A after derating from the 90 °C column and 25 A at its 75 °C terminals, so it is good for 25 A on a breaker up to 20 A.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector110.14(C)
  • Load 20 A ≤ 25 A310.14

Derating math

Table 310.16 at 90 °C
30 Aderating starts at the insulation rating
Ambient factor
× 1.0030 °C, Table 310.15(B)(1)
Bundling factor
× 1.003 current-carrying conductors, 310.15(C)(1)
Derated
30 A
Terminal limit (75 °C)
25 A110.14(C)
Allowable
25 Athe terminals decide

12 AWG

Copper 60 / 75 / 90 °C
20 / 25 / 30 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
15 / 20 / 25 A
Largest breaker (Cu, 75 °C)
20 A240.4(D) small-conductor cap
Solid diameter
0.0808"2.053 mm · ASTM B258 formula
Stranded (7 strands)
0.0920"2.337 mm · Table 8
THHN outside
0.130"3.30 mm · 0.0133 in² · Table 5
Area
6,530 cmil3.31 mm² · nearest IEC 4 mm²
DC resistance, 75 °C
1.98 Ω/1000 ftaluminum 3.25 Ω/1000 ft · Table 8
Copper weight
19.8 lb/1000 ft

20 A circuit at a glance

Wire

Copper NM-B (60 °C)
12 AWG
Copper THHN (75 °C)
12 AWG
Aluminum (75 °C)
10 AWG

Ground & breaker

Copper ground
12 AWG
Aluminum ground
10 AWG
Continuous load max
16 A
Breaker
20 A

Distance (3 %)

Cu at 120 V, 16 A
56 ft
Cu at 240 V, 16 A
113 ft
Al at 240 V, 16 A
110 ft

20 A circuit tables 7 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

20 amps:
which wire, which method.

A 20 A circuit takes 12 AWG NM-B in the wall or 12 AWG copper THHN in conduit (75 °C), with a 12 AWG ground; aluminum needs 10 AWG. At an 16 A load the copper reaches 113 ft at 240 V (3 % drop). Used for kitchen, bathroom, laundry and garage receptacles.

Three columns, three answers

NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 12 AWG NM-B and 12 AWG THHN can both serve 20 A.

Breaker rules

240.4(D) fixes the small sizes: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A, whatever the ampacity table allows.

Distance

The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.

Questions

Answered plainly.

01

What size wire for a 20 amp breaker?

+

12 AWG copper NM-B in the wall, 12 AWG copper THHN in conduit or 10 AWG aluminum, all with ampacity at least 20 A (NEC 2023 Table 310.16).

02

Can I use 12 AWG wire on a 20 amp breaker in NM-B cable?

+

Yes: 12 AWG NM-B is rated 20 A at 60 °C.

03

What size ground wire for 20 amps?

+

12 AWG copper or 10 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).

04

How far can I run a 20 amp circuit?

+

At 16 A (80 %) on 12 AWG copper, 113 ft one way at 240 V or 56 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.

05

What is the largest continuous load on a 20 amp circuit?

+

16 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).

Browse all 20 gauges, 12 conduit sizes and 10 circuits