Three columns, three answers
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 12 AWG NM-B and 12 AWG THHN can both serve 20 A.
A 20 A circuit takes 12 AWG NM-B in the wall or 12 AWG copper THHN in conduit (75 °C), with a 12 AWG ground; aluminum needs 10 AWG. At an 16 A load the copper reaches 113 ft at 240 V (3 % drop). Used for kitchen, bathroom, laundry and garage receptacles.
02 · Ampacity · NEC 2023 Table 310.16
USE:
12 AWG COPPER · 25 A ALLOWABLE · 20 A MAX BREAKER
12 AWG copper carries 30 A after derating from the 90 °C column and 25 A at its 75 °C terminals, so it is good for 25 A on a breaker up to 20 A.
Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.
| Actions | |||||
|---|---|---|---|---|---|
| 12 AWG | 12 AWG | 12 AWG | 113 ft | ||
| 12 AWG | 12 AWG | 12 AWG | 113 ft | ||
| 10 AWG | 10 AWG | 10 AWG | 110 ft |
Feet one way (the current goes out and back). Ampacity is a separate check: a long run may need a heavier wire for drop, never a lighter one for heat.
05 / Field guide
A 20 A circuit takes 12 AWG NM-B in the wall or 12 AWG copper THHN in conduit (75 °C), with a 12 AWG ground; aluminum needs 10 AWG. At an 16 A load the copper reaches 113 ft at 240 V (3 % drop). Used for kitchen, bathroom, laundry and garage receptacles.
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 12 AWG NM-B and 12 AWG THHN can both serve 20 A.
240.4(D) fixes the small sizes: 14 AWG on 15 A, 12 AWG on 20 A, 10 AWG on 30 A, whatever the ampacity table allows.
The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.
Questions
12 AWG copper NM-B in the wall, 12 AWG copper THHN in conduit or 10 AWG aluminum, all with ampacity at least 20 A (NEC 2023 Table 310.16).
Yes: 12 AWG NM-B is rated 20 A at 60 °C.
12 AWG copper or 10 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).
At 16 A (80 %) on 12 AWG copper, 113 ft one way at 240 V or 56 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.
16 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).