Three columns, three answers
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. NM-B is made only up to 2 AWG copper, so a 200 A circuit runs as THHN, XHHW or SER.
A 200 A feeder takes 3/0 AWG copper or 250 kcmil aluminum at 75 °C with a 6 AWG copper ground. A house service (or the feeder carrying the whole house) may use the 83 % rule: 2/0 AWG copper or 4/0 AWG aluminum. A 200 A subpanel feeder does not get it.
02 · Ampacity · NEC 2023 Table 310.16
USE:
3/0 AWG COPPER · 200 A ALLOWABLE · 200 A MAX BREAKER
3/0 AWG copper carries 225 A after derating from the 90 °C column and 200 A at its 75 °C terminals, so it is good for 200 A on a breaker up to 200 A.
Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.
| Actions | |||||
|---|---|---|---|---|---|
| — | — | 6 AWG | 436 ft | ||
| 3/0 AWG | 3/0 AWG | 6 AWG | 293 ft | ||
| 250 kcmil | 4/0 AWG | 4 AWG | 265 ft |
A dwelling’s 200 A service, or the feeder carrying its whole load, may use 83 % (310.12): 2/0 AWG copper or 4/0 AWG aluminum.
Feet one way (the current goes out and back). Ampacity is a separate check: a long run may need a heavier wire for drop, never a lighter one for heat.
05 / Field guide
A 200 A feeder takes 3/0 AWG copper or 250 kcmil aluminum at 75 °C with a 6 AWG copper ground. A house service (or the feeder carrying the whole house) may use the 83 % rule: 2/0 AWG copper or 4/0 AWG aluminum. A 200 A subpanel feeder does not get it.
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. NM-B is made only up to 2 AWG copper, so a 200 A circuit runs as THHN, XHHW or SER.
240.4(B) lets a conductor whose ampacity is not a standard size take the next breaker up (not on multi-outlet receptacle circuits). The headline here uses ampacity at least 200 A.
The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.
Questions
3/0 AWG copper THHN in conduit or 250 kcmil aluminum, all with ampacity at least 200 A (NEC 2023 Table 310.16).
Not at the ampacity rule: NM-B is limited to the 60 °C column (334.80), where 3/0 AWG carries 165 A; use conduit.
6 AWG copper or 4 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).
At 160 A (80 %) on 3/0 AWG copper, 293 ft one way at 240 V or 146 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.
160 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).
For a dwelling’s 200 A service, or the feeder carrying the whole dwelling, yes (310.12, 83 %). For a 200 A subpanel feeder, no: use 3/0 AWG copper or 250 kcmil aluminum.