1 AWG wire: amps, diameter & uses

1 AWG copper is 0.2893" solid (0.332" as 19-strand) and 42.4 mm². Table 310.16 rates it 110 / 130 / 145 A at 60 / 75 / 90 °C, so it protects up to a 125 A breaker on 75 °C terminals; aluminum of this size carries 100 A. Typical use: 125 A feeders and 100 A aluminum subpanels.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · caliper

1 AWG · concentric stranded copper

THIS IS:

1 AWG COPPER · 125 A BREAKER · 7.35 MM COPPER

Gauge
1 AWG
concentric stranded copper
Breaker
125 A
copper, max
Measured
8.43 mm
0.3320"

The gap is 8.43 mm (0.3320"), which reads as 1 AWG concentric stranded copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

1 AWG

Solid diameter
0.289"7.35 mm · ASTM B258 formula
Stranded (19 strands)
0.332"8.43 mm · Table 8
THHN outside
0.446"11.33 mm · 0.1562 in² · Table 5
Area
83,690 cmil42.41 mm² · nearest IEC 50 mm²
DC resistance, 75 °C
0.154 Ω/1000 ftaluminum 0.253 Ω/1000 ft · Table 8
Copper weight
253.3 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
110 / 130 / 145 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
85 / 100 / 115 A
Largest breaker (Cu, 75 °C)
125 Aampacity ≥ breaker

Other gauges

Nearest SWG
SWG 00.324" · 8.23 mm
IEC 60228
50 mm²between 35 and 50 mm²

1 AWG at a glance

Size

Solid diameter
0.2893" · 7.35 mm
Stranded (19)
0.332"
THHN outside
0.446"
Area
83,690 cmil · 42.41 mm²
Metric
35 – 50 mm²
SWG nearest
1 (7.62 mm)

Amps

Copper 60/75/90 °C
110 / 130 / 145 A
Aluminum 75 °C
100 A
Max breaker, THHN
125 A
As NM-B cable
not made
Ground for it
6 AWG

Run & fit

120 V at 100 A
116 ft at 3 %
240 V at 100 A
233 ft at 3 %
THHN in ½" EMT
1
THHN in ¾" EMT
1
Copper weight
253.3 lb/1000 ft

1 AWG reference 25 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

1 AWG
feeder copper.

1 AWG copper is 0.2893" solid (0.332" as 19-strand) and 42.4 mm². Table 310.16 rates it 110 / 130 / 145 A at 60 / 75 / 90 °C, so it protects up to a 125 A breaker on 75 °C terminals; aluminum of this size carries 100 A. Typical use: 125 A feeders and 100 A aluminum subpanels.

Between its neighbours

1 AWG has 26 % more copper than 2 AWG and 21 % less than 1/0 AWG. Its DC resistance is 0.154 Ω per 1000 ft at 75 °C (aluminum 0.253), and 1000 ft of it carries 253.3 lb of copper.

Feeders and services

1 AWG is the usual choice for 125 A feeders and 100 A aluminum subpanels. It is not made as NM-B cable; use THHN or XHHW in conduit, or SER/USE cable. The equipment ground for its largest breaker is 6 AWG.

On the 1:1 gauge

The caliper above opens at 7.35 mm. Lay a stripped length along the lines and step the gauge with ← and → until the wire just fills the gap.

Questions

Answered plainly.

01

How many amps can 1 AWG wire carry?

+

1 AWG copper is rated 110 A at 60 °C, 130 A at 75 °C and 145 A at 90 °C (NEC Table 310.16, 30 °C, three conductors or fewer). Aluminum of the same size: 100 A at 75 °C.

02

What size breaker for 1 AWG wire?

+

Up to 125 A with THHN on 75 °C terminals; the next size up is allowed by 240.4(B) only where the ampacity is not itself a standard rating.

03

What is the diameter of 1 AWG wire?

+

0.2893 inch (7.35 mm) solid, 0.332 inch stranded (19 strands), about 0.446 inch with THHN insulation.

04

What is 1 AWG in mm²?

+

42.41 mm² (83,690 circular mils). The IEC sizes either side are 35 and 50 mm²; replace it with 50 mm², not the smaller one.

05

How far can 1 AWG wire run?

+

At 100 A and 3 % drop, 116 ft one way at 120 V and 233 ft at 240 V (Table 8 resistance, 0.154 Ω per 1000 ft at 75 °C). Lighter loads go proportionally further.

06

How many 1 AWG wires fit in ½" EMT?

+

1 THHN conductors in ½" EMT, 1 in ¾" and 1 in 1" (NEC Chapter 9, 40 % fill for three or more).

07

Can 1 AWG be used for a house service?

+

Yes: by the 83 % rule (310.12) 1 AWG copper serves a dwelling’s 150 A service, or the feeder carrying its whole load. A subpanel feeder does not get the 83 % rule.

Browse all 20 gauges, 12 conduit sizes and 10 circuits