18 AWG wire: amps, diameter & uses

18 AWG wire is 0.0403" (1.02 mm) solid and 0.82 mm². It is too small for house wiring (NEC minimum 14 AWG), but as flexible cord it is rated 10 A with two current-carrying conductors; at 12 V and 5 A it reaches 4 ft at 3 % drop. Used for lamp cords, thermostat and doorbell wire, 12 V accessories.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · caliper

18 AWG · bare solid copper

THIS IS:

18 AWG COPPER · NOT BUILDING WIRE · 1.02 MM COPPER

Gauge
18 AWG
bare solid copper
Breaker
n/a
not building wire
Measured
1.02 mm
0.0403"

The gap is 1.02 mm (0.0403"), which reads as 18 AWG bare solid copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

18 AWG

Solid diameter
0.0403"1.024 mm · ASTM B258 formula
Stranded (7 strands)
0.0460"1.168 mm · Table 8
Area
1,620 cmil0.821 mm² · nearest IEC 0.75 mm²
DC resistance, 75 °C
7.95 Ω/1000 ftaluminum 13.1 Ω/1000 ft · Table 8
Copper weight
4.90 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
— / — / 14 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
—
Largest breaker (Cu, 75 °C)
—ampacity ≥ breaker

Other gauges

Nearest SWG
SWG 190.04" · 1.016 mm
IEC 60228
0.75 mm²between 0.75 and 1 mm²

18 AWG at a glance

Size

Solid diameter
0.0403" · 1.02 mm
Stranded (7)
0.046"
Area
1,620 cmil · 0.821 mm²
Metric
0.75 – 1 mm²
SWG nearest
19 (1.016 mm)

Amps

Copper 60/75/90 °C
— / — / 14 A
Aluminum 75 °C
—
Max breaker, THHN
—
As NM-B cable
not made
Ground for it
—

Run & fit

120 V at 5 A
45 ft at 3 %
240 V at 5 A
90 ft at 3 %
THHN in ½" EMT
null
THHN in ¾" EMT
null
Copper weight
4.9 lb/1000 ft

18 AWG reference 18 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

18 AWG
cords and low voltage.

18 AWG wire is 0.0403" (1.02 mm) solid and 0.82 mm². It is too small for house wiring (NEC minimum 14 AWG), but as flexible cord it is rated 10 A with two current-carrying conductors; at 12 V and 5 A it reaches 4 ft at 3 % drop. Used for lamp cords, thermostat and doorbell wire, 12 V accessories.

Between its neighbours

18 AWG has 59 % more copper than 20 AWG and 37 % less than 16 AWG. Its DC resistance is 7.95 Ω per 1000 ft at 75 °C (aluminum 13.1), and 1000 ft of it carries 4.90 lb of copper.

Feeders and services

18 AWG is the usual choice for lamp cords, thermostat and doorbell wire, 12 V accessories. It is not made as NM-B cable; use THHN or XHHW in conduit, or SER/USE cable. The equipment ground for its largest breaker is null.

On the 1:1 gauge

The caliper above opens at 1.02 mm. Lay a stripped length along the lines and step the gauge with ← and → until the wire just fills the gap.

Questions

Answered plainly.

01

How many amps can 18 AWG wire carry?

+

18 AWG copper is rated — A at 60 °C, null A at 75 °C and 14 A at 90 °C (NEC Table 310.16, 30 °C, three conductors or fewer). Aluminum of the same size: — A at 75 °C.

02

What size breaker for 18 AWG wire?

+

Up to null A with THHN on 75 °C terminals.

03

What is the diameter of 18 AWG wire?

+

0.0403 inch (1.02 mm) solid, 0.046 inch stranded (7 strands).

04

What is 18 AWG in mm²?

+

0.821 mm² (1,620 circular mils). The IEC sizes either side are 0.75 and 1 mm²; replace it with 1 mm², not the smaller one.

05

How far can 18 AWG wire run?

+

At 5 A and 3 % drop, 45 ft one way at 120 V and 90 ft at 240 V (Table 8 resistance, 7.95 Ω per 1000 ft at 75 °C). Lighter loads go proportionally further.

06

How far can 18 AWG speaker wire run?

+

About 31 ft to an 8 Ω speaker and 15 ft to a 4 Ω one before the cable passes 5 % of the impedance (about 0.42 dB).

07

What is 18 AWG in SWG?

+

The nearest British Standard Wire Gauge is SWG 19 at 1.016 mm, against 1.02 mm for 18 AWG.

Browse all 20 gauges, 12 conduit sizes and 10 circuits