Three columns, three answers
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 3 AWG NM-B and 4 AWG THHN can both serve 80 A.
A 80 A circuit takes 3 AWG NM-B in the wall or 4 AWG copper THHN in conduit (75 °C), with a 8 AWG ground; aluminum needs 2 AWG. At an 64 A load the copper reaches 182 ft at 240 V (3 % drop). Used for subpanels and 64 A EV chargers.
02 · Ampacity · NEC 2023 Table 310.16
USE:
4 AWG COPPER · 85 A ALLOWABLE · 80 A MAX BREAKER
4 AWG copper carries 95 A after derating from the 90 °C column and 85 A at its 75 °C terminals, so it is good for 85 A on a breaker up to 80 A.
Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.
| Actions | |||||
|---|---|---|---|---|---|
| 3 AWG | 3 AWG | 8 AWG | 229 ft | ||
| 4 AWG | 4 AWG | 8 AWG | 182 ft | ||
| 2 AWG | 3 AWG | 6 AWG | 176 ft |
Feet one way (the current goes out and back). Ampacity is a separate check: a long run may need a heavier wire for drop, never a lighter one for heat.
05 / Field guide
An 80 A circuit takes 3 AWG NM-B in the wall or 4 AWG copper THHN in conduit (75 °C), with an 8 AWG ground; aluminum needs 2 AWG. At an 64 A load the copper reaches 182 ft at 240 V (3 % drop). Used for subpanels and 64 A EV chargers.
NM-B cable is held to the 60 °C column, THHN in conduit on 60/75 °C breakers uses 75 °C. That is why 3 AWG NM-B and 4 AWG THHN can both serve 80 A.
240.4(B) lets a conductor whose ampacity is not a standard size take the next breaker up (not on multi-outlet receptacle circuits). The headline here uses ampacity at least 80 A.
The answer above is the minimum for heat. On a long run upsize for voltage drop, and grow the ground with it: the table below gives the longest 240 V run at 3 % for each candidate size.
Questions
3 AWG copper NM-B in the wall, 4 AWG copper THHN in conduit or 2 AWG aluminum, all with ampacity at least 80 A (NEC 2023 Table 310.16).
Not at the ampacity rule: NM-B is limited to the 60 °C column (334.80), where 4 AWG carries 70 A; use 3 AWG.
8 AWG copper or 6 AWG aluminum (Table 250.122), larger in proportion if the circuit wire is upsized for distance (250.122(B)).
At 64 A (80 %) on 4 AWG copper, 182 ft one way at 240 V or 91 ft at 120 V before the drop passes 3 %. Beyond that, go up a size.
64 A: a continuous load (3 hours or more) may use only 80 % of the breaker rating (the 125 % rule).