Low-voltage DC carries a lot of current for its power, so the drop decides the gauge long before heat does. ABYC E-11 sets the marine limits most installers borrow: 3 % for critical circuits (navigation lights, bilge blowers, electronics, panel feeders) and 10 % for lighting and other non-critical loads.
Out and back
The current goes to the load and back, so a 15 ft run is 30 ft of conductor (or the chassis on a car). At 12 V, 3 % is just 0.36 V: 10 AWG carries 20 A only 7 ft, 6 AWG 18 ft. At 24 V the same wire goes twice as far.
max one-way ft = (pct ÷ 100 × V × 1000) ÷ (2 × I × R Ω/1000 ft)
Ampacity still applies
The site checks the gauge against NEC Table 310.16 at 90 °C as a conservative ceiling; 105 °C automotive and marine cable carries more. Fuse every positive run at the battery.
Car amps and solar
Size a car amplifier’s power wire for its fuse rating, not its advertised watts. For solar, the panel-to-controller run is a continuous load: keep it at 3 % or less, or move to 24 or 48 V.
Fuses, grounds and terminals
Fuse every positive conductor as close to the battery as practical, sized to protect the wire, not the load. In a car the return is the chassis: keep the ground strap short, to bare metal, and as heavy as the power wire. On a boat, ABYC E-11 calls for a dedicated return conductor rather than the hull.
Crimp terminals with the tool their maker specifies and seal them with adhesive-lined heat shrink where moisture can reach; a poor crimp adds more resistance than several feet of cable.
Solar and 24 V systems
For solar PV the NEC sizes conductors at 125 % of the maximum circuit current, which is itself 125 % of the panel’s short-circuit current (690.8), so 156 % of Isc in all. The drop rules above still apply. Moving a system from 12 V to 24 V doubles the reach of every gauge: 10 AWG carries 20 A 7 ft at 12 V but 14 ft at 24 V at the same 3 %.