01How many 12 AWG wires fit in 1 1/2" EMT?
+−
61 THHN conductors at the 40 % limit (0.814 in² ÷ 0.0133 in²); 61 current-carrying 12 AWG are derated to 35 % (310.15(C)(1)).
02How many 10 AWG wires fit in 1 1/2" EMT?
+−
38 THHN, or 33 XHHW (thicker insulation, 0.0243 in² against 0.0211 in²).
03How often does 1 1/2" EMT need a strap?
+−
Within 3 ft of every box or fitting and at least every 10 ft along the run (NEC 358.30): a 50 ft straight run takes 6 straps, a 100 ft run 11. Keep the bends between pull points to 360° or less (358.26).
04Can I run a 60 amp subpanel in 1 1/2" EMT?
+−
Three 6 AWG THHN and a 10 AWG ground take 0.1732 in², 8.5 % of 2.036 in²: that fits the 40 % limit.
05What is the inside diameter of 1 1/2" EMT?
+−
1.610 inch nominal (NEC Chapter 9 Table 4), 1.740 inch outside. Use the inside area, 2.036 in², for fill.
06What is the largest wire that fits 1 1/2" EMT three at a time?
+−
3/0 AWG THHN: three fit within 40 %.
07Is 1 1/2" EMT bigger inside than EMT?
+−
EMT is the reference: 1 1/2" EMT has 2.036 in² inside.