Every breaker,
its wire.
A sheet for each common breaker size from 15 to 200 amps. Each gives the copper NM-B, copper THHN and aluminum sizes with ampacity at least the breaker rating, the Table 250.122 ground, the longest run at 3 percent drop, the 125 percent continuous-load limit and, at 100 A and up, the 83 percent rule for a house service.
| Breaker | Cu NM-B | Cu THHN | Aluminum | Ground | 240 V run |
|---|---|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG | 14 AWG | 95 ft |
| 20 A | 12 AWG | 12 AWG | 10 AWG | 12 AWG | 113 ft |
| 30 A | 10 AWG | 10 AWG | 8 AWG | 10 AWG | 120 ft |
| 40 A | 8 AWG | 8 AWG | 8 AWG | 10 AWG | 144 ft |
| 50 A | 6 AWG | 8 AWG | 6 AWG | 10 AWG | 115 ft |
| 60 A | 4 AWG | 6 AWG | 4 AWG | 10 AWG | 152 ft |
| 70 A | 4 AWG | 4 AWG | 3 AWG | 8 AWG | 208 ft |
| 80 A | 3 AWG | 4 AWG | 2 AWG | 8 AWG | 182 ft |
| 100 A | — | 3 AWG | 1 AWG | 8 AWG | 183 ft |
| 200 A | — | 3/0 AWG | 250 kcmil | 6 AWG | 293 ft |
NM-B is made only up to 2 AWG copper. Runs are one way at 80 % of the breaker rating.