wire&amp home

Every breaker,
its wire.

A sheet for each common breaker size from 15 to 200 amps. Each gives the copper NM-B, copper THHN and aluminum sizes with ampacity at least the breaker rating, the Table 250.122 ground, the longest run at 3 percent drop, the 125 percent continuous-load limit and, at 100 A and up, the 83 percent rule for a house service.

Wire size for 15 to 200 amp breakers: copper NM-B at 60 °C, copper THHN and aluminum at 75 °C, copper ground and the longest 240 V run at 3 % drop on 80 % load
BreakerCu NM-BCu THHNAluminumGround240 V run
15 A14 AWG14 AWG12 AWG14 AWG95 ft
20 A12 AWG12 AWG10 AWG12 AWG113 ft
30 A10 AWG10 AWG8 AWG10 AWG120 ft
40 A8 AWG8 AWG8 AWG10 AWG144 ft
50 A6 AWG8 AWG6 AWG10 AWG115 ft
60 A4 AWG6 AWG4 AWG10 AWG152 ft
70 A4 AWG4 AWG3 AWG8 AWG208 ft
80 A3 AWG4 AWG2 AWG8 AWG182 ft
100 A—3 AWG1 AWG8 AWG183 ft
200 A—3/0 AWG250 kcmil6 AWG293 ft

NM-B is made only up to 2 AWG copper. Runs are one way at 80 % of the breaker rating.

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →