Ampacity
Flexible cord ratings with two current-carrying conductors (column B): 16 AWG 13 A, 14 AWG 18 A, 12 AWG 25 A, 10 AWG 30 A. The plug and receptacle usually limit a cord set to 15 A anyway.
Extension cord gauge chart: a cord must carry the current and keep the voltage up. 16 AWG is rated 13 A, 14 AWG 18 A, 12 AWG 25 A (Table 400.5(A)(1)). A 13 A saw needs 16 AWG at 50 ft and 12 AWG at 100 ft to stay under 5 % drop at 120 V.
04 · Extension cord gauge
USE:
16 AWG EXTENSION CORD (16/3) · 13 A CORD RATING · 50 FT MAX
A 13 A load 50 ft from the outlet needs at least 16 AWG cord to stay under 5 % drop at 120 V and within the cord’s 13 A rating.
Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.
| Actions | ||||||
|---|---|---|---|---|---|---|
| 600 | 16 AWG | 16 AWG | 16 AWG | 14 AWG | ||
| 960 | 16 AWG | 16 AWG | 14 AWG | 12 AWG | ||
| 1200 | 16 AWG | 16 AWG | 14 AWG | 12 AWG | ||
| 1440 | 16 AWG | 16 AWG | 12 AWG | 12 AWG | ||
| 1560 | 16 AWG | 16 AWG | 12 AWG | 10 AWG | ||
| 1800 | 14 AWG | 14 AWG | 12 AWG | 10 AWG | ||
| 1920 | 14 AWG | 14 AWG | 12 AWG | 10 AWG | ||
| 2400 | 12 AWG | 12 AWG | 10 AWG | 8 AWG |
Cord ratings (column B, two current-carrying conductors): 16 AWG 13 A, 14 AWG 18 A, 12 AWG 25 A, 10 AWG 30 A. Plugs limit most cord sets to 15 A.
| Actions | ||||||
|---|---|---|---|---|---|---|
| 600 | 16 AWG | 16 AWG | 14 AWG | 12 AWG | ||
| 960 | 16 AWG | 16 AWG | 12 AWG | 10 AWG | ||
| 1200 | 16 AWG | 14 AWG | 12 AWG | 10 AWG | ||
| 1440 | 16 AWG | 14 AWG | 10 AWG | 8 AWG | ||
| 1560 | 16 AWG | 14 AWG | 10 AWG | 8 AWG | ||
| 1800 | 14 AWG | 12 AWG | 10 AWG | 8 AWG | ||
| 1920 | 14 AWG | 12 AWG | 10 AWG | 8 AWG | ||
| 2400 | 12 AWG | 12 AWG | 8 AWG | 6 AWG |
Cord ratings (column B, two current-carrying conductors): 16 AWG 13 A, 14 AWG 18 A, 12 AWG 25 A, 10 AWG 30 A. Plugs limit most cord sets to 15 A.
| 18 AWG | 7 A | 10 A | 7.95 |
|---|---|---|---|
| 16 AWG | 10 A | 13 A | 4.99 |
| 14 AWG | 15 A | 18 A | 3.14 |
| 12 AWG | 20 A | 25 A | 1.98 |
| 10 AWG | 25 A | 30 A | 1.24 |
| 8 AWG | 35 A | 40 A | 0.778 |
| 6 AWG | 45 A | 55 A | 0.491 |
| 4 AWG | 60 A | 70 A | 0.308 |
| 2 AWG | 80 A | 95 A | 0.194 |
Correct for ambient temperatures other than 30 °C with Table 310.15(B)(1); more than three current-carrying conductors in one cord use 400.5(A)(2).
05 / Field guide
An extension cord has to carry the current without overheating and deliver enough voltage that the tool keeps its speed. NEC Table 400.5(A)(1) gives the first limit; resistance and length give the second, and on long cords it is the one that decides.
Flexible cord ratings with two current-carrying conductors (column B): 16 AWG 13 A, 14 AWG 18 A, 12 AWG 25 A, 10 AWG 30 A. The plug and receptacle usually limit a cord set to 15 A anyway.
The chart keeps the drop under 5 % at 120 V with stranded copper at room temperature. A 13 A saw takes 16 AWG at 25 ft, 16 AWG at 50 ft, 12 AWG at 100 ft and 10 AWG at 150 ft.
V drop = 2 × L × I × R 5 % of 120 V = 6 V
Uncoil a cord before running a heater or compressor on it; a coiled cord cannot shed heat. Cords are temporary wiring (400.12): they are not a substitute for a circuit.
The letters on a cord tell you where it can go. S is service grade, J junior (300 V), T thermoplastic, O an oil-resistant jacket (OO adds oil-resistant insulation), W weather-rated for outdoor use. SJTW is a common outdoor cord; SJOOW is a tougher rubber cord for job sites. The numbers give the gauge and conductor count: 12/3 is three 12 AWG conductors, including the ground.
Outdoors, use a cord whose jacket letters end in W and plug it into a GFCI-protected receptacle; dwelling outdoor receptacles must have GFCI protection (210.8(A)(3)). Keep connections off wet ground or in a listed cover, and never run a cord through a doorway, window or under a rug, where damage goes unseen and the cord cannot shed heat. Replace a cord with a cut jacket rather than taping it.
A 30 A, 120/240 V generator inlet (NEMA L14-30) takes a four-conductor cord: two hots, a neutral and a ground. Only two conductors carry current at a time on a balanced load, so 10 AWG cord, rated 30 A in column B, is the usual choice. A 30 A RV cord (TT-30) is 10/3; a 50 A RV cord is 6/3 plus 8 AWG, sold as a finished cord set.
Questions
14 AWG up to 25 ft, 14 AWG to 50 ft and 12 AWG to 100 ft.
For lamps, chargers and small tools up to 13 A on short runs, yes. Not for heaters, compressors or saws on long runs.
A 1500 W heater draws 12.5 A; most makers say not to use a cord at all. If you must, use a heavy 12 or 14 AWG cord, short and uncoiled.
12 AWG conductors, three of them (hot, neutral and ground). Only two carry current, so the cord uses column B of Table 400.5(A)(1).
Voltage drop. Motors draw more current when the voltage falls, which makes the drop worse; use a heavier gauge or a shorter cord.
Service grade, junior (300 V), thermoplastic jacket, weather-rated. It is suitable for outdoor use; for job sites a rubber SJOOW cord lasts longer.
A 10/4 cord for a 120/240 V L14-30 inlet, or 10/3 for a 120 V TT-30 RV outlet; 10 AWG cord is rated 30 A with two current-carrying conductors.