Wire gauge chart & 1:1 screen sizer

Wire gauge chart from 40 AWG to 500 kcmil with diameter, mm², amps and a true-size screen caliper. 12 AWG is 2.05 mm of copper, good for 20 A. Or skip the math: a 48 A EV charger takes 6 AWG copper THHN on a 60 A breaker in 3/4" EMT, or 4 AWG NM-B in the wall.

Drawing at true size…

Quick Project Finder · 48 A EV

EV charger, 48 A hardwired · 50 ft one way, THHN copper in EMT

USE:

6 AWG COPPER WIRE · 60 A 2-POLE BREAKER · 3/4" EMT CONDUIT

Wire
6 AWG
copper THHN
Breaker
60 A
2-pole
Conduit
3/4" EMT
ground 10 AWG

Safe for up to 65 A (75 °C THHN terminals) on a 60 A breaker, and carries a continuous 48 A load up to 152 feet one way with under 3% voltage drop.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector110.14(C)
  • Continuous load × 125 % = 60 A ≤ 65 A625.40
  • 0.98 % drop at 50 ft210.19 IN

The answer

Wire
2 × 6 AWG THHN copper + 10 AWG groundTHHN copper in EMT
Breaker
60 A 2-pole2-pole, 240 V
Ground
10 AWG copperTable 250.122 for 60 A
Conduit
3/4" EMT23.0 % full of 40 %
Max distance at this size
152 ft one wayunder 3 % drop at 48 A

How it was worked out

Allowable ampacity
65 A6 AWG, 75 °C column
Load used for the drop
48 A continuousEV charging is a continuous load
Smallest size before distance
6 AWG
With In-wall NM-B cable
4 AWGNM-B is limited to the 60 °C column

6 AWG

Copper 60 / 75 / 90 °C
55 / 65 / 75 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
40 / 50 / 55 A
Largest breaker (Cu, 75 °C)
60 Aampacity ≥ breaker
Solid diameter
0.162"4.12 mm · ASTM B258 formula
Stranded (7 strands)
0.184"4.67 mm · Table 8
THHN outside
0.254"6.45 mm · 0.0507 in² · Table 5
Area
26,240 cmil13.30 mm² · nearest IEC 16 mm²

Wire gauge reference 67 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

Copper first,
then the code.

A wire gauge is a size of metal, not of plastic. American Wire Gauge numbers run backwards and shrink by a fixed ratio: every 6 gauges the diameter halves, every 3 gauges the area halves. 10 AWG is 2.59 mm of copper, 12 AWG 2.05 mm, 14 AWG 1.63 mm. The chart, the 1:1 caliper and the quick finder above all read from the same tables: NEC 2023 Table 310.16 for amps, Chapter 9 for diameters and resistance.

The AWG formula

AWG (Brown & Sharpe) defines 36 AWG as 0.005 inch and 4/0 as 0.4600 inch, with 39 equal ratio steps between them. That makes the formula below exact for solid wire, and it is why 4/0, 3/0, 2/0 and 1/0 continue the scale past 1 AWG before kcmil (thousands of circular mils) take over at 250.

Stranded wire of the same gauge has the same copper area but a larger outside diameter: 7 strands up to 2 AWG, 19 strands from 1 AWG to 4/0 and 37 strands from 250 to 500 kcmil (NEC Chapter 9 Table 8).

d (in) = 0.005 × 92^((36 − n) / 39) 4/0 = n −3 · 1/0 = n 0 area (cmil) = (1000 × d)²

Three answers for the same wire

Table 310.16 gives every size three ampacities, at 60, 75 and 90 °C. 6 AWG copper is 55 A as NM-B cable (334.80 holds NM-B to 60 °C), 65 A as THHN on 60/75 °C breakers and lugs, and 75 A at 90 °C, a number you may derate from but never use at a terminal.

That is the trap behind the most common homeowner question: a 48 A EV charger is a continuous load and needs 60 A of ampacity, so 6 AWG THHN in conduit works and 6 AWG NM-B (55 A) does not; in the wall it takes 4 AWG NM-B.

Why the screen can be trusted

A browser does not know how big its pixels are, so the gauge starts from a table of 114 phones, tablets, laptops and monitors matched to your screen’s size and pixel ratio, an estimate good to about five percent. Laying a coin or a bank card on the glass and matching its outline replaces the estimate with a measurement good to a fraction of a percent, saved for this screen only.

Browser zoom is corrected automatically from the pixel ratio; pinch zoom is flagged, because nothing drawn is true size until it is undone.

pixels per mm = CSS px across the card ÷ 85.60 mm ID-1 card: 85.60 × 53.98 mm (ISO/IEC 7810)

Questions

Answered plainly.

01

What size wire for a 20 amp circuit?

+

12 AWG copper. 240.4(D) caps 12 AWG at a 20 A breaker whatever the table says, and 14 AWG is capped at 15 A. A long run may need 10 AWG for voltage drop: 12 AWG reaches about 56 ft one way at 16 A and 3 %.

02

How thick is 12 gauge wire?

+

12 AWG solid copper is 0.0808 inch (2.05 mm). Stranded 12 AWG is about 0.092 inch, and with THHN insulation about 0.130 inch (3.3 mm) across the jacket.

03

What does a higher gauge number mean?

+

A thinner wire. AWG counts drawing steps, so 18 AWG is thinner than 12 AWG; each 6 steps halves the diameter. Above 1 AWG the scale continues as 1/0, 2/0, 3/0 and 4/0, then kcmil.

04

What size wire for a 48 amp EV charger?

+

6 AWG copper THHN in conduit on a 60 A breaker (3/4" EMT), or 4 AWG NM-B in the wall. The charger is continuous, so the circuit must be 125 % of 48 A.

05

Can I measure wire on my phone screen?

+

Yes, once the screen is calibrated with a coin or a card. Lay the stripped wire along the caliper lines and close the jaw until it just fills the gap. Below about 24 AWG a pixel is too coarse; wind 10 turns on a pencil and measure the coil instead.

06

Is the gauge the same for copper and aluminum?

+

The diameters are the same, the ampacity is not. Aluminum carries about 78 % of copper’s current at the same size, so it is used a size or two larger: a 100 A feeder is 3 AWG copper or 1 AWG aluminum.

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →