Sizing a wire is two checks in a row. First ampacity: the conductor must carry the breaker rating (or 125 % of a continuous load) at the right temperature column. Then voltage drop: on a long run the same current loses enough voltage that a heavier wire is worth it. If the drop forces a larger wire, 250.122(B) makes the ground grow in the same proportion.
Voltage drop
The drop is the current times the resistance of the whole loop, out and back for DC and single phase, √3 times one leg for three phase. The calculator uses NEC Chapter 9 Table 8 DC resistance at 75 °C, which lands on the same size as Cerrowire’s AC tables or one size heavier, never lighter.
A 30 A, 240 V dryer reaches 120 ft one way on 10 AWG at 3 % (24 A running); a 20 A, 120 V garage circuit at 16 A reaches 56 ft on 12 AWG and 90 ft on 10 AWG.
V drop = 2 × L (ft) × I × R (Ω/1000 ft) ÷ 1000 3-phase: √3 × L × I × R ÷ 1000 % = V drop ÷ V × 100
3 % and 5 % are recommendations
The NEC’s 3 % for a branch circuit and 5 % for feeder plus branch are informational notes (210.19(A) IN No. 4, 215.2(A) IN No. 2): good practice, not an enforceable rule. Sensitive loads, motors and long outbuilding runs are where they matter.
Grow the ground too
250.122(B): when you upsize the circuit conductors for distance, increase the wire-type equipment grounding conductor by the same circular-mil ratio. 6 → 4 AWG on a 60 A circuit multiplies the area by 1.59, so the 10 AWG ground becomes 8 AWG.
Worked example: a 100 A subpanel 150 ft away
At 80 A of load and 240 V, the 75 °C minimum for a 100 A feeder is 3 AWG copper or 1 AWG aluminum. Over 150 ft the drop pushes the copper to 3 AWG (2.5 %) and the aluminum to 1 AWG (2.5 %), and the ground grows with it to 6 AWG aluminum or 8 AWG copper. Aluminum feeders are usually the cheaper choice at this size, terminated on lugs rated for aluminum and torqued to the marked value.