NEC 2023 Table 310.16 ampacity for copper and aluminum at 60, 75 and 90 °C, with derating. 6 AWG copper is 55 A as NM-B cable but 65 A as THHN on 75 °C terminals. Nine 12 AWG THHN in one raceway at 40 °C drop from 30 A to 19.1 A.

Drawing at true size…

02 · Ampacity · NEC 2023 Table 310.16

6 AWG copper · 90 °C insulation, 75 °C terminals, 30 °C, 3 conductors

USE:

6 AWG COPPER · 65 A ALLOWABLE · 60 A MAX BREAKER

Allowable
65 A
6 AWG Cu
Max breaker
60 A
ampacity ≥ breaker
For your load
8 AWG
50 A

6 AWG copper carries 75 A after derating from the 90 °C column and 65 A at its 75 °C terminals, so it is good for 65 A on a breaker up to 60 A.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector110.14(C)
  • Load 50 A ≤ 65 A310.14

Derating math

Table 310.16 at 90 °C
75 Aderating starts at the insulation rating
Ambient factor
× 1.0030 °C, Table 310.15(B)(1)
Bundling factor
× 1.003 current-carrying conductors, 310.15(C)(1)
Derated
75 A
Terminal limit (75 °C)
65 A110.14(C)
Allowable
65 Athe terminals decide

6 AWG

Copper 60 / 75 / 90 °C
55 / 65 / 75 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
40 / 50 / 55 A
Largest breaker (Cu, 75 °C)
60 Aampacity ≥ breaker
Solid diameter
0.162"4.12 mm · ASTM B258 formula
Stranded (7 strands)
0.184"4.67 mm · Table 8
THHN outside
0.254"6.45 mm · 0.0507 in² · Table 5
Area
26,240 cmil13.30 mm² · nearest IEC 16 mm²
DC resistance, 75 °C
0.491 Ω/1000 ftaluminum 0.808 Ω/1000 ft · Table 8
Copper weight
79.4 lb/1000 ft

NEC ampacity tables 58 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

One table,
three temperatures.

NEC Table 310.16 lists the current a conductor may carry with no more than three current-carrying conductors in a raceway or cable at 30 °C. Every size has a 60 °C, 75 °C and 90 °C column, and which one you may use depends on the insulation, the wiring method and the weakest termination. The calculator applies them in that order.

Derate from 90 °C, stop at the terminals

Correction for a hot attic or a crowded conduit starts from the insulation’s own column (90 °C for THHN), so the derating has some headroom. The result is then capped at the column of the terminations, which 110.14(C) sets at 60 °C for circuits of 100 A or less unless the equipment is marked 75 °C (most breakers and lugs today are marked 60/75 °C).

Example: nine 12 AWG THHN in one conduit in a 40 °C space: 30 A × 0.91 × 0.70 = 19.1 A, below the 25 A terminal limit, so 19.1 A it is: a 15 A breaker, or 20 A only where the 240.4(B) next-size-up rule applies.

allowable = min( 310.16[insulation °C] × ambient factor × bundling factor , 310.16[terminal °C] )

Small-conductor caps

240.4(D) caps the breaker on small copper no matter what the table says: 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A (and 12 AWG aluminum 15 A, 10 AWG aluminum 25 A).

240.4(B) lets a conductor whose ampacity is not a standard breaker size take the next size up, up to 800 A, except on multi-outlet receptacle circuits: 6 AWG NM-B (55 A) may go on a 60 A breaker.

NEC 2026

The 2026 edition adds rows for 16 AWG copper and 14 AWG copper-clad aluminum to Table 310.16 (310.5(A) lowers the minimum sizes) and moves the load calculations from Article 220 to Article 120. Building-wire ampacities are unchanged; this site cites NEC 2023, the edition most jurisdictions enforce.

Worked example: a 40 A circuit through a hot attic

8 AWG THHN copper is 55 A at 90 °C. In a 50 °C attic the ambient factor for the 90 °C column is 0.82, so it carries 45.1 A, still under its 50 A terminal limit: the allowable is 45.1 A and a 40 A breaker is fine. The same 8 AWG as NM-B starts from the same 55 A for derating but is capped at the 60 °C column, 40 A. Run more than three current-carrying conductors through the same attic and the bundling factor stacks on top.

Questions

Answered plainly.

01

What is the ampacity of 10 AWG copper?

+

30 A at 60 °C, 35 A at 75 °C and 40 A at 90 °C, but 240.4(D) limits it to a 30 A breaker. As NM-B cable it is 30 A.

02

Why is NM-B limited to 60 °C?

+

NEC 334.80 sets the ampacity of NM cable at the 60 °C column, even though its conductors are rated 90 °C. The 90 °C rating may be used only as the starting point for derating.

03

How much does aluminum carry compared with copper?

+

About 78 %. 1 AWG aluminum is 100 A at 75 °C against 130 A for copper, which is why aluminum feeders run a size or two larger.

04

When do I derate for more than three wires?

+

When more than three current-carrying conductors share a raceway or cable longer than 24 inches: 4–6 conductors 80 %, 7–9 70 %, 10–20 50 % (Table 310.15(C)(1)). Grounds do not count, and a neutral carrying only the unbalanced current does not count.

05

What is a continuous load?

+

A load that runs three hours or more, like an EV charger, a spa heater or store lighting. The circuit must be sized for 125 % of it (210.19(A)(1), 215.2(A)(1)).

06

Which edition of the NEC does this use?

+

NEC 2023, with notes where NEC 2026 changes a row. Your jurisdiction adopts an edition, sometimes with amendments; check with the local inspector.

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →