Ground wire size chart (NEC 250.122 & 250.66)

Ground wire size by NEC Table 250.122: a 60 A breaker needs 10 AWG copper, 100 An 8 AWG, 200 A 6 AWG. Upsize the circuit for distance and the ground grows too (250.122(B)): 6 → 4 AWG takes it to 8 AWG. Services use Table 250.66.

Drawing at true size…

Quick Project Finder · 100 A subpanel

Subpanel, 100 A · 200 ft one way, THHN copper in EMT

USE:

2 AWG COPPER WIRE · 100 A 2-POLE BREAKER · 1 1/4" EMT CONDUIT

Wire
2 AWG
copper THHN
Breaker
100 A
2-pole
Conduit
1 1/4" EMT
ground 6 AWG

Safe for up to 115 A (75 °C THHN terminals) on a 100 A breaker, and carries a 80 A load up to 231 feet one way with under 3% voltage drop.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector110.14(C)
  • 2.59 % drop at 200 ft210.19 IN
  • Upsized from 3 AWG for distance; ground 8 AWG → 6 AWG250.122(B)

The answer

Wire
3 × 2 AWG THHN copper + 6 AWG groundTHHN copper in EMT
Breaker
100 A 2-pole2-pole, 240 V
Ground
6 AWG copperTable 250.122 for 100 A, grown with the wire
Conduit
1 1/4" EMT26.6 % full of 40 %
Max distance at this size
231 ft one wayunder 3 % drop at 80 A

How it was worked out

Allowable ampacity
115 A2 AWG, 75 °C column
Load used for the drop
80 AA 100 A subpanel feeder, four wires. Aluminum is the usual, cheaper choice at th
Smallest size before distance
3 AWG
With Aluminum SER / XHHW-2
3 AWG75 °C terminals allow the THHN column

2 AWG

Copper 60 / 75 / 90 °C
95 / 115 / 130 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
75 / 90 / 100 A
Largest breaker (Cu, 75 °C)
110 Aampacity ≥ breaker
Solid diameter
0.258"6.54 mm · ASTM B258 formula
Stranded (7 strands)
0.292"7.42 mm · Table 8
THHN outside
0.384"9.75 mm · 0.1158 in² · Table 5
Area
66,360 cmil33.63 mm² · nearest IEC 35 mm²

Grounding conductor tables 30 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

Sized by the breaker,
grown with the wire.

The equipment grounding conductor carries fault current long enough for the breaker to trip, so NEC Table 250.122 sizes it by the breaker or fuse protecting the circuit, not by the circuit wire. The grounding electrode conductor that ties a service to its ground rod or footing steel is a different wire, sized by Table 250.66 from the service conductors.

Table 250.122

15 A: 14 AWG copper. 20 A: 12. 30–60 A: 10. 100 A: 8 AWG. 200 A: 6 AWG. 400 A: 3 AWG. Aluminum runs two sizes larger. 250.122(A): never required larger than the circuit conductors.

Upsizing for distance: 250.122(B)

When the circuit conductors are made larger than the minimum to cut voltage drop, the wire ground grows by the same circular-mil ratio. A 60 A circuit moved from 6 to 4 AWG grows by 1.59×: the 10 AWG ground (10,380 cmil) must reach 16,511 cmil, which is 8 AWG.

ground cmil ≥ Table 250.122 ground cmil × (installed wire cmil ÷ minimum wire cmil)

Table 250.66

A 200 A service on 2/0 AWG copper takes a 4 AWG copper grounding electrode conductor; the conductor to a ground rod alone never needs to exceed 6 AWG copper (250.66(A)), to a concrete-encased electrode 4 AWG (250.66(B)).

Detached buildings and subpanels

A feeder to a detached garage or shop runs four wires: two hots, a neutral and an equipment grounding conductor sized by Table 250.122. At the remote panel the neutral and ground stay separate, and the building gets its own grounding electrode, usually ground rods bonded to the panel (250.32). The same separation applies to any subpanel in the house.

Parallel runs, colours and old circuits

Where a feeder runs in parallel through several raceways, each raceway gets its own full-size grounding conductor from Table 250.122, based on the breaker for the whole feeder (250.122(F)). A grounding conductor is bare, green or green with yellow stripes (250.119). For a 100 A feeder upsized from 3 AWG to 1/0 copper, the 8 AWG ground grows to 4 AWG.

An old two-wire circuit without a ground can be protected by a GFCI and its receptacles labelled “No equipment ground” (406.4(D)(2)); the GFCI protects people but does not replace a ground for surge protectors or equipment that needs one.

Questions

Answered plainly.

01

What size ground wire for a 100 amp subpanel?

+

8 AWG copper or 6 AWG aluminum by Table 250.122, larger if the feeder was upsized for distance. The subpanel keeps neutral and ground separate.

02

What size ground wire for a 200 amp service?

+

The grounding electrode conductor is 4 AWG copper for 2/0 AWG copper service conductors (Table 250.66), or 6 AWG copper to rods only. Equipment grounds for 200 A feeders are 6 AWG copper.

03

Does the ground wire have to be the same size as the hots?

+

No. It is sized by the breaker (Table 250.122), so it is often smaller, but never required larger than the circuit conductors.

04

Can the ground be bare?

+

Yes, in cables like NM-B and in most raceways; some installations (spas, some feeders) require an insulated copper ground.

05

Why does the ground get bigger on a long run?

+

A longer, heavier circuit can deliver more fault current; 250.122(B) keeps the ground able to carry it so the breaker trips quickly.

06

Does a detached garage need a ground rod?

+

Yes. A building supplied by a feeder needs its own grounding electrode system (250.32), bonded to the equipment grounding conductor at its panel; the neutral is not bonded there.

07

What color is the ground wire?

+

Bare copper, green, or green with one or more yellow stripes (250.119). Larger conductors may be re-identified with green tape at each end.

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →