Table 250.122
15 A: 14 AWG copper. 20 A: 12. 30–60 A: 10. 100 A: 8 AWG. 200 A: 6 AWG. 400 A: 3 AWG. Aluminum runs two sizes larger. 250.122(A): never required larger than the circuit conductors.
Ground wire size by NEC Table 250.122: a 60 A breaker needs 10 AWG copper, 100 An 8 AWG, 200 A 6 AWG. Upsize the circuit for distance and the ground grows too (250.122(B)): 6 → 4 AWG takes it to 8 AWG. Services use Table 250.66.
Quick Project Finder · 100 A subpanel
USE:
2 AWG COPPER WIRE · 100 A 2-POLE BREAKER · 1 1/4" EMT CONDUIT
Safe for up to 115 A (75 °C THHN terminals) on a 100 A breaker, and carries a 80 A load up to 231 feet one way with under 3% voltage drop.
Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.
| Actions | |||
|---|---|---|---|
| 14 AWG | 12 AWG | ||
| 12 AWG | 10 AWG | ||
| 10 AWG | 8 AWG | ||
| 10 AWG | 8 AWG | ||
| 10 AWG | 8 AWG | ||
| 8 AWG | 6 AWG | ||
| 6 AWG | 4 AWG | ||
| 4 AWG | 2 AWG | ||
| 3 AWG | 1 AWG | ||
| 2 AWG | 1/0 AWG | ||
| 1 AWG | 2/0 AWG | ||
| 1/0 AWG | 3/0 AWG | ||
| 2/0 AWG | 4/0 AWG | ||
| 3/0 AWG | 250 kcmil |
Never required larger than the circuit conductors (250.122(A)); grows in proportion when they are upsized (250.122(B)).
| 20 A | 12 AWG | 10 AWG | × 1.59 | 12 AWG | 10 AWG |
|---|---|---|---|---|---|
| 20 A | 12 AWG | 8 AWG | × 2.53 | 12 AWG | 8 AWG |
| 30 A | 10 AWG | 8 AWG | × 1.59 | 10 AWG | 8 AWG |
| 30 A | 10 AWG | 6 AWG | × 2.53 | 10 AWG | 6 AWG |
| 50 A | 8 AWG | 6 AWG | × 1.59 | 10 AWG | 8 AWG |
| 60 A | 6 AWG | 4 AWG | × 1.59 | 10 AWG | 8 AWG |
| 60 A | 6 AWG | 2 AWG | × 2.53 | 10 AWG | 6 AWG |
| 100 A | 3 AWG | 1 AWG | × 1.59 | 8 AWG | 6 AWG |
| 100 A | 3 AWG | 1/0 AWG | × 2.01 | 8 AWG | 4 AWG |
| 200 A | 3/0 AWG | 250 kcmil | × 1.49 | 6 AWG | 4 AWG |
| 2 or smaller | 1/0 or smaller | 8 AWG | 6 AWG |
|---|---|---|---|
| 1 or 1/0 | 2/0 or 3/0 | 6 AWG | 4 AWG |
| 2/0 or 3/0 | 4/0 or 250 | 4 AWG | 2 AWG |
| Over 3/0 through 350 | Over 250 through 500 | 2 AWG | 1/0 AWG |
| Over 350 through 600 | Over 500 through 900 | 1/0 AWG | 3/0 AWG |
| Over 600 through 1100 | Over 900 through 1750 | 2/0 AWG | 4/0 AWG |
A conductor to a rod, pipe or plate electrode alone is never required larger than 6 AWG copper (250.66(A)); to a concrete-encased electrode, 4 AWG (250.66(B)).
05 / Field guide
The equipment grounding conductor carries fault current long enough for the breaker to trip, so NEC Table 250.122 sizes it by the breaker or fuse protecting the circuit, not by the circuit wire. The grounding electrode conductor that ties a service to its ground rod or footing steel is a different wire, sized by Table 250.66 from the service conductors.
15 A: 14 AWG copper. 20 A: 12. 30–60 A: 10. 100 A: 8 AWG. 200 A: 6 AWG. 400 A: 3 AWG. Aluminum runs two sizes larger. 250.122(A): never required larger than the circuit conductors.
When the circuit conductors are made larger than the minimum to cut voltage drop, the wire ground grows by the same circular-mil ratio. A 60 A circuit moved from 6 to 4 AWG grows by 1.59×: the 10 AWG ground (10,380 cmil) must reach 16,511 cmil, which is 8 AWG.
ground cmil ≥ Table 250.122 ground cmil × (installed wire cmil ÷ minimum wire cmil)
A 200 A service on 2/0 AWG copper takes a 4 AWG copper grounding electrode conductor; the conductor to a ground rod alone never needs to exceed 6 AWG copper (250.66(A)), to a concrete-encased electrode 4 AWG (250.66(B)).
A feeder to a detached garage or shop runs four wires: two hots, a neutral and an equipment grounding conductor sized by Table 250.122. At the remote panel the neutral and ground stay separate, and the building gets its own grounding electrode, usually ground rods bonded to the panel (250.32). The same separation applies to any subpanel in the house.
Where a feeder runs in parallel through several raceways, each raceway gets its own full-size grounding conductor from Table 250.122, based on the breaker for the whole feeder (250.122(F)). A grounding conductor is bare, green or green with yellow stripes (250.119). For a 100 A feeder upsized from 3 AWG to 1/0 copper, the 8 AWG ground grows to 4 AWG.
An old two-wire circuit without a ground can be protected by a GFCI and its receptacles labelled “No equipment ground” (406.4(D)(2)); the GFCI protects people but does not replace a ground for surge protectors or equipment that needs one.
Questions
8 AWG copper or 6 AWG aluminum by Table 250.122, larger if the feeder was upsized for distance. The subpanel keeps neutral and ground separate.
The grounding electrode conductor is 4 AWG copper for 2/0 AWG copper service conductors (Table 250.66), or 6 AWG copper to rods only. Equipment grounds for 200 A feeders are 6 AWG copper.
No. It is sized by the breaker (Table 250.122), so it is often smaller, but never required larger than the circuit conductors.
Yes, in cables like NM-B and in most raceways; some installations (spas, some feeders) require an insulated copper ground.
A longer, heavier circuit can deliver more fault current; 250.122(B) keeps the ground able to carry it so the breaker trips quickly.
Yes. A building supplied by a feeder needs its own grounding electrode system (250.32), bonded to the equipment grounding conductor at its panel; the neutral is not bonded there.
Bare copper, green, or green with one or more yellow stripes (250.119). Larger conductors may be re-identified with green tape at each end.