14 AWG wire: amps, diameter & uses

14 AWG copper is 0.0641" (1.63 mm) across and 2.08 mm², between 1.5 and 2.5 mm² metric. It is rated 15 / 20 / 25 A at 60 / 75 / 90 °C and takes a 15 A breaker (the 240.4(D) cap). Used for 15 A lighting and bedroom circuits.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · caliper

14 AWG · bare solid copper

THIS IS:

14 AWG COPPER · 15 A BREAKER · 1.63 MM COPPER

Gauge
14 AWG
bare solid copper
Breaker
15 A
copper, max
Measured
1.63 mm
0.0641"

The gap is 1.63 mm (0.0641"), which reads as 14 AWG bare solid copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

14 AWG

Solid diameter
0.0641"1.628 mm · ASTM B258 formula
Stranded (7 strands)
0.0730"1.854 mm · Table 8
THHN outside
0.111"2.82 mm · 0.0097 in² · Table 5
Area
4,110 cmil2.08 mm² · nearest IEC 2.5 mm²
DC resistance, 75 °C
3.14 Ω/1000 ftaluminum 5.17 Ω/1000 ft · Table 8
Copper weight
12.4 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
15 / 20 / 25 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
—
Largest breaker (Cu, 75 °C)
15 A240.4(D) small-conductor cap

Other gauges

Nearest SWG
SWG 160.064" · 1.626 mm
IEC 60228
2.5 mm²between 1.5 and 2.5 mm²

14 AWG at a glance

Size

Solid diameter
0.0641" · 1.63 mm
Stranded (7)
0.073"
THHN outside
0.111"
Area
4,110 cmil · 2.08 mm²
Metric
1.5 – 2.5 mm²
SWG nearest
16 (1.626 mm)

Amps

Copper 60/75/90 °C
15 / 20 / 25 A
Aluminum 75 °C
—
Max breaker, THHN
15 A
As NM-B cable
15 A · white
Ground for it
14 AWG

Run & fit

120 V at 12 A
47 ft at 3 %
240 V at 12 A
95 ft at 3 %
THHN in ½" EMT
12
THHN in ¾" EMT
22
Copper weight
12.4 lb/1000 ft

14 AWG reference 20 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

14 AWG
the branch-circuit size.

14 AWG copper is 0.0641" (1.63 mm) across and 2.08 mm², between 1.5 and 2.5 mm² metric. It is rated 15 / 20 / 25 A at 60 / 75 / 90 °C and takes a 15 A breaker (the 240.4(D) cap). Used for 15 A lighting and bedroom circuits.

Between its neighbours

14 AWG has 59 % more copper than 16 AWG and 37 % less than 12 AWG. Its DC resistance is 3.14 Ω per 1000 ft at 75 °C (aluminum 5.17), and 1000 ft of it carries 12.4 lb of copper.

Circuits it is used for

14 AWG is the usual choice for 15 A lighting and bedroom circuits. As NM-B it comes as 14/2 and 14/3 with a white jacket, held to the 60 °C column (15 A). The equipment ground for its largest breaker is 14 AWG.

On the 1:1 gauge

The caliper above opens at 1.63 mm. Lay a stripped length along the lines and step the gauge with ← and → until the wire just fills the gap.

Questions

Answered plainly.

01

How many amps can 14 AWG wire carry?

+

14 AWG copper is rated 15 A at 60 °C, 20 A at 75 °C and 25 A at 90 °C (NEC Table 310.16, 30 °C, three conductors or fewer). 240.4(D) still limits it to a 15 A breaker. Aluminum of the same size: — A at 75 °C.

02

What size breaker for 14 AWG wire?

+

Up to 15 A with THHN on 75 °C terminals, 15 A as NM-B cable (60 °C).

03

What is the diameter of 14 AWG wire?

+

0.0641 inch (1.63 mm) solid, 0.073 inch stranded (7 strands), about 0.111 inch with THHN insulation.

04

What is 14 AWG in mm²?

+

2.08 mm² (4,110 circular mils). The IEC sizes either side are 1.5 and 2.5 mm²; replace it with 2.5 mm², not the smaller one.

05

How far can 14 AWG wire run?

+

At 12 A and 3 % drop, 47 ft one way at 120 V and 95 ft at 240 V (Table 8 resistance, 3.14 Ω per 1000 ft at 75 °C). Lighter loads go proportionally further.

06

How many 14 AWG wires fit in ½" EMT?

+

12 THHN conductors in ½" EMT, 22 in ¾" and 35 in 1" (NEC Chapter 9, 40 % fill for three or more).

07

How far can 14 AWG speaker wire run?

+

About 79 ft to an 8 Ω speaker and 39 ft to a 4 Ω one before the cable passes 5 % of the impedance (about 0.42 dB).

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →