01How many 12 AWG wires fit in 3/4" PVC Schedule 80?
+−
12 THHN conductors at the 40 % limit (0.164 in² ÷ 0.0133 in²); 12 current-carrying 12 AWG are derated to 50 % (310.15(C)(1)).
02How many 10 AWG wires fit in 3/4" PVC Schedule 80?
+−
7 THHN, or 6 XHHW (thicker insulation, 0.0243 in² against 0.0211 in²).
03How often does 3/4" PVC Schedule 80 need a strap?
+−
Within 3 ft of every box or fitting and at least every 3 ft along the run (NEC 352.30, Table 352.30): a 50 ft straight run takes 16 straps, a 100 ft run 33. Keep the bends between pull points to 360° or less (352.26).
04Can I run a 60 amp subpanel in 3/4" PVC Schedule 80?
+−
Three 6 AWG THHN and a 10 AWG ground take 0.1732 in², 42.3 % of 0.409 in²: over the 40 % limit; use 1" PVC 80.
05What is the inside diameter of 3/4" PVC Schedule 80?
+−
0.722 inch nominal (NEC Chapter 9 Table 4), 1.050 inch outside. Use the inside area, 0.409 in², for fill.
06What is the largest wire that fits 3/4" PVC Schedule 80 three at a time?
+−
6 AWG THHN: three fit within 40 %.
07Is 3/4" PVC Schedule 80 bigger inside than EMT?
+−
23 % smaller than 3/4" EMT (0.533 in²): the thick wall of Schedule 80 costs inside room.