Conduit fill calculator & chart

Conduit fill calculator for EMT, PVC Schedule 40 and 80, IMC, RMC, FMC, LFMC and ENT with a live cross-section of the wires packed inside. ½" EMT takes 9 × 12 AWG THHN, ¾" EMT 16, ½" PVC 40 8, at the 40 % limit of NEC Chapter 9 Table 1 (53 % for one wire, 31 % for two).

Drawing at true size…

03 · Conduit fill · Chapter 9 Tables 1, 4 & 5

3/4" EMT · 4 conductors

USE:

3/4" EMT · 10.0% FILL · PASS

Fill
10.0 %
limit 40 %
Smallest that fits
1/2"
EMT
Most of this wire
16
12 THHN

4 conductors take 0.0532 in² of the 0.533 in² inside 3/4" EMT: 10.0 % against the 40 % allowed.

  • Meets NEC 2023 Chapter 9 Table 1 — verify with your local AHJ/inspectorCh. 9 Table 1

Fill math

4 × 12 THHN
0.0532 in²0.0133 in² each · Table 5
Conduit area
0.533 in²ID 0.824" · Table 4
Allowed (40 %)
0.213 in²

Conduit fill tables 57 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

Room to pull,
not just room to fit.

Conduit fill limits exist so wire can be pulled without stripping its insulation and so it can shed heat. NEC Chapter 9 Table 1 allows 53 % of the inside area for one conductor, 31 % for two and 40 % for three or more; Table 4 gives the inside area of every raceway and Table 5 the area of every insulated wire.

How the count is worked out

Add the Table 5 area of every conductor, including the insulated ground, and compare it with the allowed share of the Table 4 area. ½" EMT has 0.304 in² inside, so 40 % is 0.122 in²: 9 × 12 AWG THHN (0.0133 in² each) fit, 5 × 10 AWG.

Note 7: when every conductor is the same size and the count works out to a fraction of .8 or more, round up. That is why two 6 AWG THHN fit in ½" EMT: 31 % of 0.304 in² ÷ 0.0507 in² = 1.85, which rounds to 2.

fill % = Σ (Table 5 area × count) ÷ Table 4 total area limit: 1 wire 53 % · 2 wires 31 % · 3+ 40 % · nipple ≤ 24" 60 %

Jamming

Three conductors of one size can wedge in a bend when the conduit’s inside diameter is 2.8 to 3.2 times the wire’s outside diameter (Chapter 9 Table 1, Informational Note 2). The calculator flags it; a size up, or a fourth conductor, avoids it.

The drawing

The cross-section packs the conductors bottom-up, the way a pull settles in a horizontal run. It is drawn to scale, not 1:1; the fullscreen mat in Mode 01 draws ½" to 2" EMT and PVC outside diameters at true size.

Straps, supports and bends

Every raceway has a securing rule and a support spacing. EMT is secured within 3 ft of each box and supported at least every 10 ft (358.30); PVC within 3 ft and then every 3 ft for ½" to 1" or 5 ft for 1¼" to 2" (Table 352.30); flexible metal conduit within 1 ft and every 4.5 ft (348.30). A straight 50 ft run of EMT therefore takes 6 straps, of 1" PVC 16.

Between pull points (boxes and conduit bodies) the bends may total 360°, the same as four quarter bends, in every raceway type (358.26, 352.26, 348.26, 344.26). Offsets and kicks count too: a 30° offset is 60° of bend. PVC also needs expansion fittings where the temperature swing would move a long straight run (352.44).

Questions

Answered plainly.

01

How many 12 gauge wires fit in ½ inch EMT?

+

9 THHN conductors (40 % of 0.304 in²). In ¾" EMT, 16; in 1" EMT, 26. Remember the derating for more than three current-carrying conductors.

02

Does the ground wire count in conduit fill?

+

Yes. Every conductor in the raceway counts toward fill, including the equipment grounding conductor; bare grounds use their Table 8 area. Grounds do not count for ampacity derating.

03

Is PVC conduit smaller inside than EMT?

+

Schedule 40 PVC is slightly smaller than EMT at ½" (0.285 vs 0.304 in²) and Schedule 80, with its thicker wall, much smaller (0.217 in²). The outside diameters are larger, which matters for knockouts and straps.

04

What is the 60 percent rule?

+

Chapter 9 Note 4: a nipple 24 inches long or shorter between boxes or enclosures may be filled to 60 %, and its conductors are not derated for bundling.

05

What is ENT?

+

Electrical nonmetallic tubing, the flexible blue corrugated raceway (“smurf tube”). 362.20(B) stops it at trade size 2; its Table 4 dimensions match PVC Schedule 40 in the current tables.

06

How many bends are allowed in a conduit run?

+

No more than 360° in total between pull points, the same as four 90° bends. Count offsets as two bends each; add a pull box or conduit body before you exceed it.

07

How far apart do conduit straps go?

+

EMT every 10 ft and within 3 ft of each box; PVC every 3 ft for ½"–1" and 5 ft for 1¼"–2" (Table 352.30); flexible metal conduit every 4.5 ft and within 12 in of each box.

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →