01How many 12 AWG wires fit in 1/2" PVC Schedule 40?
+−
8 THHN conductors at the 40 % limit (0.114 in² ÷ 0.0133 in²); 8 current-carrying 12 AWG are derated to 70 % (310.15(C)(1)).
02How many 10 AWG wires fit in 1/2" PVC Schedule 40?
+−
5 THHN, or 4 XHHW (thicker insulation, 0.0243 in² against 0.0211 in²).
03How often does 1/2" PVC Schedule 40 need a strap?
+−
Within 3 ft of every box or fitting and at least every 3 ft along the run (NEC 352.30, Table 352.30): a 50 ft straight run takes 16 straps, a 100 ft run 33. Keep the bends between pull points to 360° or less (352.26).
04Can I run a 60 amp subpanel in 1/2" PVC Schedule 40?
+−
Three 6 AWG THHN and a 10 AWG ground take 0.1732 in², 60.8 % of 0.285 in²: over the 40 % limit; use 3/4" PVC 40.
05What is the inside diameter of 1/2" PVC Schedule 40?
+−
0.602 inch nominal (NEC Chapter 9 Table 4), 0.840 inch outside. Use the inside area, 0.285 in², for fill.
06What is the largest wire that fits 1/2" PVC Schedule 40 three at a time?
+−
8 AWG THHN: three fit within 40 %.
07Is 1/2" PVC Schedule 40 bigger inside than EMT?
+−
6 % smaller than 1/2" EMT (0.304 in²).