3 AWG wire: amps, diameter & uses

3 AWG copper is 0.2294" solid (0.26" as 7-strand) and 26.7 mm². Table 310.16 rates it 85 / 100 / 115 A at 60 / 75 / 90 °C, so it protects up to a 100 A breaker on 75 °C terminals; aluminum of this size carries 75 A. Typical use: 100 A copper subpanels.

1:1 · reading this screen…
Drawing at true size…

01 · 1:1 wire gauge · caliper

3 AWG · concentric stranded copper

THIS IS:

3 AWG COPPER · 100 A BREAKER · 5.83 MM COPPER

Gauge
3 AWG
concentric stranded copper
Breaker
100 A
copper, max
Measured
6.60 mm
0.2600"

The gap is 6.60 mm (0.2600"), which reads as 3 AWG concentric stranded copper. Measure bare copper for the gauge: insulation is far thicker than the metal.

  • Meets NEC 2023 Table 310.16 at 75°C — verify with your local AHJ/inspector310.16
  • Drawn at true sizecalibrated screen

3 AWG

Solid diameter
0.229"5.83 mm · ASTM B258 formula
Stranded (7 strands)
0.260"6.60 mm · Table 8
THHN outside
0.352"8.94 mm · 0.0973 in² · Table 5
Area
52,620 cmil26.66 mm² · nearest IEC 25 mm²
DC resistance, 75 °C
0.245 Ω/1000 ftaluminum 0.403 Ω/1000 ft · Table 8
Copper weight
159.3 lb/1000 ft

Ampacity

Copper 60 / 75 / 90 °C
85 / 100 / 115 ANM-B uses the 60 °C column (334.80)
Aluminum 60 / 75 / 90 °C
65 / 75 / 85 A
Largest breaker (Cu, 75 °C)
100 Aampacity ≥ breaker

Other gauges

Nearest SWG
SWG 30.252" · 6.401 mm
IEC 60228
25 mm²between 25 and 35 mm²

3 AWG at a glance

Size

Solid diameter
0.2294" · 5.83 mm
Stranded (7)
0.26"
THHN outside
0.352"
Area
52,620 cmil · 26.66 mm²
Metric
25 – 35 mm²
SWG nearest
4 (5.893 mm)

Amps

Copper 60/75/90 °C
85 / 100 / 115 A
Aluminum 75 °C
75 A
Max breaker, THHN
100 A
As NM-B cable
not made
Ground for it
8 AWG

Run & fit

120 V at 80 A
91 ft at 3 %
240 V at 80 A
183 ft at 3 %
THHN in ½" EMT
1
THHN in ¾" EMT
1
Copper weight
159.3 lb/1000 ft

3 AWG reference 25 rows

Sort any column, print a shop sheet, download CSV. Click a row to load it in the calculator.

05 / Field guide

3 AWG
feeder copper.

3 AWG copper is 0.2294" solid (0.26" as 7-strand) and 26.7 mm². Table 310.16 rates it 85 / 100 / 115 A at 60 / 75 / 90 °C, so it protects up to a 100 A breaker on 75 °C terminals; aluminum of this size carries 75 A. Typical use: 100 A copper subpanels.

Between its neighbours

3 AWG has 26 % more copper than 4 AWG and 21 % less than 2 AWG. Its DC resistance is 0.245 Ω per 1000 ft at 75 °C (aluminum 0.403), and 1000 ft of it carries 159.3 lb of copper.

Feeders and services

3 AWG is the usual choice for 100 A copper subpanels. It is not made as NM-B cable; use THHN or XHHW in conduit, or SER/USE cable. The equipment ground for its largest breaker is 8 AWG.

On the 1:1 gauge

The caliper above opens at 5.83 mm. Lay a stripped length along the lines and step the gauge with ← and → until the wire just fills the gap.

Questions

Answered plainly.

01

How many amps can 3 AWG wire carry?

+

3 AWG copper is rated 85 A at 60 °C, 100 A at 75 °C and 115 A at 90 °C (NEC Table 310.16, 30 °C, three conductors or fewer). Aluminum of the same size: 75 A at 75 °C.

02

What size breaker for 3 AWG wire?

+

Up to 100 A with THHN on 75 °C terminals; the next size up is allowed by 240.4(B) only where the ampacity is not itself a standard rating.

03

What is the diameter of 3 AWG wire?

+

0.2294 inch (5.83 mm) solid, 0.26 inch stranded (7 strands), about 0.352 inch with THHN insulation.

04

What is 3 AWG in mm²?

+

26.66 mm² (52,620 circular mils). The IEC sizes either side are 25 and 35 mm²; replace it with 35 mm², not the smaller one.

05

How far can 3 AWG wire run?

+

At 80 A and 3 % drop, 91 ft one way at 120 V and 183 ft at 240 V (Table 8 resistance, 0.245 Ω per 1000 ft at 75 °C). Lighter loads go proportionally further.

06

How many 3 AWG wires fit in ½" EMT?

+

1 THHN conductors in ½" EMT, 1 in ¾" and 3 in 1" (NEC Chapter 9, 40 % fill for three or more).

Browse all 20 gauges, 12 conduit sizes and 10 circuits

Every gauge in one table →