01How many 12 AWG wires fit in 2" EMT?
+−
101 THHN conductors at the 40 % limit (1.342 in² ÷ 0.0133 in², rounded up by Note 7); 101 current-carrying 12 AWG are derated to 35 % (310.15(C)(1)).
02How many 10 AWG wires fit in 2" EMT?
+−
63 THHN, or 55 XHHW (thicker insulation, 0.0243 in² against 0.0211 in²).
03How often does 2" EMT need a strap?
+−
Within 3 ft of every box or fitting and at least every 10 ft along the run (NEC 358.30): a 50 ft straight run takes 6 straps, a 100 ft run 11. Keep the bends between pull points to 360° or less (358.26).
04Can I run a 60 amp subpanel in 2" EMT?
+−
Three 6 AWG THHN and a 10 AWG ground take 0.1732 in², 5.2 % of 3.356 in²: that fits the 40 % limit.
05What is the inside diameter of 2" EMT?
+−
2.067 inch nominal (NEC Chapter 9 Table 4), 2.197 inch outside. Use the inside area, 3.356 in², for fill.
06What is the largest wire that fits 2" EMT three at a time?
+−
300 kcmil THHN: three fit within 40 %.
07Is 2" EMT bigger inside than EMT?
+−
EMT is the reference: 2" EMT has 3.356 in² inside.